    <TITLE>Test medium.</TITLE>
    <GRANULENUM>195.306</GRANULENUM>
    <HEADING>Section 195.306</HEADING>
    <ANCESTORS>
      <PARENT HEADING="Title 49" SEQ="4">Transportation</PARENT>
      <PARENT HEADING="Subtitle B" SEQ="3">Other Regulations Relating to Transportation (Continued)</PARENT>
      <PARENT HEADING="SUBCHAPTER D" SEQ="2">PIPELINE SAFETY</PARENT>
      <PARENT HEADING="PART 195" SEQ="1">TRANSPORTATION OF HAZARDOUS LIQUIDS BY PIPELINE</PARENT>
      <PARENT HEADING="Subpart E" SEQ="0">Pressure Testing</PARENT>
    </ANCESTORS>
  </FDSYS>
  <SECTION>
    <SECTNO>§ 195.306</SECTNO>
    <SUBJECT>Test medium.</SUBJECT>
    <P>(a) Except as provided in paragraphs (b), (c), and (d) of this section, water must be used as the test medium.</P>
    <P>(b) Except for offshore pipelines, liquid petroleum that does not vaporize rapidly may be used as the test medium if—</P>
    <P>(1) The entire pipeline section under test is outside of cities and other populated areas;</P>
    <P>(2) Each building within 300 feet (91 meters) of the test section is unoccupied while the test pressure is equal to or greater than a pressure which produces a hoop stress of 50 percent of specified minimum yield strength;</P>
    <P>(3) The test section is kept under surveillance by regular patrols during the test; and</P>

    <P>(4) Continuous communication is maintained along entire test section.<PRTPAGE P="148"/>
    </P>
    <P>(c) Carbon dioxide pipelines may use inert gas or carbon dioxide as the test medium if—</P>
    <P>(1) The entire pipeline section under test is outside of cities and other populated areas;</P>
    <P>(2) Each building within 300 feet (91 meters) of the test section is unoccupied while the test pressure is equal to or greater than a pressure that produces a hoop stress of 50 percent of specified minimum yield strength;</P>
    <P>(3) The maximum hoop stress during the test does not exceed 80 percent of specified minimum yield strength;</P>
    <P>(4) Continuous communication is maintained along entire test section; and</P>
    <P>(5) The pipe involved is new pipe having a longitudinal joint factor of 1.00.</P>
    <P>(d) Air or inert gas may be used as the test medium in low-stress pipelines.</P>
    <CITA>[Amdt. 195-22, 46 FR 38360, July 27, 1991, as amended by Amdt. 195-45, 56 FR 26926, June 12, 1991; Amdt. 195-51, 59 FR 29385, June 7, 1994; Amdt. 195-53, 59 FR 35471, July 12, 1994; Amdt. 195-51A, 59 FR 41260, Aug. 11, 1994; Amdt. 195-63, 63 FR 37506, July 13, 1998]</CITA>