    <TITLE>Interim prohibition for deferred UST systems.</TITLE>
    <GRANULENUM>280.11</GRANULENUM>
    <HEADING>Section 280.11</HEADING>
    <ANCESTORS>
      <PARENT HEADING="Title 40" SEQ="4">Protection of Environment</PARENT>
      <PARENT HEADING="CHAPTER I" SEQ="3">ENVIRONMENTAL PROTECTIONAGENCY (CONTINUED)</PARENT>
      <PARENT HEADING="SUBCHAPTER I" SEQ="2">SOLID WASTES (CONTINUED)</PARENT>
      <PARENT HEADING="PART 280" SEQ="1">TECHNICAL STANDARDS AND CORRECTIVE ACTION REQUIREMENTS FOR OWNERS AND OPERATORS OF UNDERGROUND STORAGE TANKS (UST)</PARENT>
      <PARENT HEADING="Subpart A" SEQ="0">Program Scope and Interim Prohibition</PARENT>
    </ANCESTORS>
  </FDSYS>
  <SECTION>
    <SECTNO>§ 280.11</SECTNO>
    <SUBJECT>Interim prohibition for deferred UST systems.</SUBJECT>
    <P>(a) No person may install an UST system listed in § 280.10(c) for the purpose of storing regulated substances unless the UST system (whether of single- or double-wall construction):</P>
    <P>(1) Will prevent releases due to corrosion or structural failure for the operational life of the UST system;</P>
    <P>(2) Is cathodically protected against corrosion, constructed of noncorrodible material, steel clad with a noncorrodible material, or designed in a manner to prevent the release or threatened release of any stored substance; and</P>
    <P>(3) Is constructed or lined with material that is compatible with the stored substance.</P>
    <P>(b) Notwithstanding paragraph (a) of this section, an UST system without corrosion protection may be installed at a site that is determined by a corrosion expert not to be corrosive enough to cause it to have a release due to corrosion during its operating life. Owners and operators must maintain records that demonstrate compliance with the requirements of this paragraph for the remaining life of the tank.</P>
    <NOTE>
      <HD SOURCE="HED">Note:</HD>

      <P>The National Association of Corrosion Engineers Standard RP-02-85, “Control of External Corrosion on Metallic Buried, <PRTPAGE P="453"/>Partially Buried, or Submerged Liquid Storage Systems,” may be used as guidance for complying with paragraph (b) of this section.</P>