<?xml version="1.0"?>
<?xml-stylesheet type="text/xsl" href="cfr.xsl"?>
<CFRGRANULE xmlns:xsi="http://www.w3.org/2001/XMLSchema-instance" xsi:noNamespaceSchemaLocation="CFRMergedXML.xsd">
  <FDSYS>
    <CFRTITLE>40</CFRTITLE>
    <CFRTITLETEXT>Protection of Environment</CFRTITLETEXT>
    <VOL>6</VOL>
    <DATE>2008-07-01</DATE>
    <ORIGINALDATE>2008-07-01</ORIGINALDATE>
    <COVERONLY>false</COVERONLY>
    <TITLE>Standard for mercury (Hg).</TITLE>
    <GRANULENUM>60.45Da</GRANULENUM>
    <HEADING>Section 60.45Da</HEADING>
    <ANCESTORS>
      <PARENT HEADING="Title 40" SEQ="4">Protection of Environment</PARENT>
      <PARENT HEADING="CHAPTER I" SEQ="3">ENVIRONMENTAL PROTECTION AGENCY (CONTINUED)</PARENT>
      <PARENT HEADING="SUBCHAPTER C" SEQ="2">AIR PROGRAMS (CONTINUED)</PARENT>
      <PARENT HEADING="PART 60" SEQ="1">STANDARDS OF PERFORMANCE FOR NEW STATIONARY SOURCES</PARENT>
      <PARENT HEADING="Subpart Da" SEQ="0">Standards of Performance for Electric Utility Steam Generating Units for Which Construction is Commenced After September 18, 1978</PARENT>
    </ANCESTORS>
  </FDSYS>
  <SECTION>
    <SECTNO>§ 60.45Da</SECTNO>
    <SUBJECT>Standard for mercury (Hg).</SUBJECT>
    <P>(a) For each coal-fired electric utility steam generating unit other than an IGCC electric utility steam generating unit, on and after the date on which the initial performance test is completed or required to be completed under § 60.8, whichever date comes first, no owner or operator subject to the provisions of this subpart shall cause to be discharged into the atmosphere from any affected facility for which construction, modification, or reconstruction commenced after January 30, 2004, any gases that contain mercury (Hg) emissions in excess of each Hg emissions limit in paragraphs (a)(1) through (5) of this section that applies to you. The Hg emissions limits in paragraphs (a)(1) through (5) of this section are based on a 12-month rolling average basis using the procedures in § 60.50Da(h).</P>

    <P>(1) For each coal-fired electric utility steam generating unit that burns only bituminous coal, you must not discharge into the atmosphere any gases from a new affected source that contain Hg in excess of 20 × 10<E T="51">−</E>
      <SU>6</SU> pound per <PRTPAGE P="140"/>megawatt hour (lb/MWh) or 0.020 lb/gigawatt-hour (GWh) on an output basis. The International System of Units (SI) equivalent is 0.0025 ng/J.</P>
    <P>(2) For each coal-fired electric utility steam generating unit that burns only subbituminous coal:</P>

    <P>(i) If your unit is located in a county-level geographical area receiving greater than 25 inches per year (in/yr) mean annual precipitation, based on the most recent publicly available U.S. Department of Agriculture 30-year data, you must not discharge into the atmosphere any gases from a new affected source that contain Hg in excess of 66 × 10<E T="51">−</E>
      <SU>6</SU> lb/MWh or 0.066 lb/GWh on an output basis. The SI equivalent is 0.0083 ng/J.</P>

    <P>(ii) If your unit is located in a county-level geographical area receiving less than or equal to 25 in/yr mean annual precipitation, based on the most recent publicly available U.S. Department of Agriculture 30-year data, you must not discharge into the atmosphere any gases from a new affected source that contain Hg in excess of 97 × 10<E T="51">−</E>
      <SU>6</SU> lb/MWh or 0.097 lb/GWh on an output basis. The SI equivalent is 0.0122 ng/J.</P>

    <P>(3) For each coal-fired electric utility steam generating unit that burns only lignite, you must not discharge into the atmosphere any gases from a new affected source that contain Hg in excess of 175 × 10<E T="51">−</E>
      <SU>6</SU> lb/MWh or 0.175 lb/GWh on an output basis. The SI equivalent is 0.0221 ng/J.</P>

    <P>(4) For each coal-burning electric utility steam generating unit that burns only coal refuse, you must not discharge into the atmosphere any gases from a new affected source that contain Hg in excess of 16 × 10<E T="51">−</E>
      <SU>6</SU> lb/MWh or 0.016 lb/GWh on an output basis. The SI equivalent is 0.0020 ng/J.</P>

    <P>(5) For each coal-fired electric utility steam generating unit that burns a blend of coals from different coal ranks (<E T="03">i.e.</E>, bituminous coal, subbituminous coal, lignite) or a blend of coal and coal refuse, you must not discharge into the atmosphere any gases from a new affected source that contain Hg in excess of the unit-specific Hg emissions limit established according to paragraph (a)(5)(i) or (ii) of this section, as applicable to the affected unit.</P>
    <P>(i) If you operate a coal-fired electric utility steam generating unit that burns a blend of coals from different coal ranks or a blend of coal and coal refuse, you must not discharge into the atmosphere any gases from a new affected source that contain Hg in excess of the computed weighted Hg emissions limit based on the Btu, MWh, or MJ) contributed by each coal rank burned during the compliance period and its applicable Hg emissions limit in paragraphs (a)(1) through (4) of this section as determined using Equation 1 in this section. For each affected source, you must comply with the weighted Hg emissions limit calculated using Equation 1 in this section based on the total Hg emissions from the unit and the total Btu, MWh, or MJ contributed by all fuels burned during the compliance period.</P>
    <MATH DEEP="57" SPAN="1">
      <MID>ER13JN07.011</MID>
    </MATH>
    <EXTRACT>
      <FP>Where:</FP>
      
      <FP SOURCE="FP-1">EL<E T="52">b</E> = Total allowable Hg in lb/MWh that can be emitted to the atmosphere from any affected source being averaged according to this paragraph.</FP>
      <FP SOURCE="FP-1">EL<E T="52">i</E> = Hg emissions limit for the subcategory i (coal rank) that applies to affected source, lb/MWh;</FP>
      <FP SOURCE="FP-1">HH<E T="52">i</E> = For each affected source, the Btu, MWh, or MJ contributed by the corresponding subcategory i (coal rank) burned during the compliance period; and</FP>
      <FP SOURCE="FP-1">n = Number of subcategories (coal ranks) being averaged for an affected source.</FP>
    </EXTRACT>
    

    <P>(ii) If you operate a coal-fired electric utility steam generating unit that burns a blend of coals from different coal ranks or a blend of coal and coal refuse together with one or more non-regulated, supplementary fuels, you must not discharge into the atmosphere any gases from a new affected source that contain Hg in excess of the computed weighted Hg emission limit based on the Btu, MWh, or MJ contributed by each coal rank burned during the compliance period and its applicable Hg emissions limit in paragraphs (a)(1) through (4) of this section as determined using Equation 1 in this section. For each affected source. You <PRTPAGE P="141"/>must comply with the weighted Hg emissions limit calculated using Equation 1 in this section based on the total Hg emissions from the unit contributed by both regulated and nonregulated fuels burned during the compliance period and the total Btu, MWh, or MJ contributed by both regulated and nonregulated fuels burned during the compliance period.</P>

    <P>(b) For each IGCC electric utility steam generating unit, on and after the date on which the initial performance test required to be conducted under § 60.8 is completed, no owner or operator subject to the provisions of this subpart shall cause to be discharged into the atmosphere from any affected facility for which construction, modification, or reconstruction commenced after January 30, 2004, any gases that contain Hg emissions in excess of 20 × 10<E T="51">−</E>
      <SU>6</SU> lb/MWh or 0.020 lb/GWh on an output basis. The SI equivalent is 0.0025 ng/J. This Hg emissions limit is based on a 12-month rolling average basis using the procedures in § 60.50Da(h).</P>
  </SECTION>
</CFRGRANULE>