[Title 40 CFR 60.274a]
[Code of Federal Regulations (annual edition) - July 1, 2009 Edition]
[Title 40 - PROTECTION OF ENVIRONMENT]
[Chapter I - ENVIRONMENTAL PROTECTION AGENCY (CONTINUED)]
[Subchapter C - AIR PROGRAMS (CONTINUED)]
[Part 60 - STANDARDS OF PERFORMANCE FOR NEW STATIONARY SOURCES--]
[Subpart Aaa - Standards of Performance for Steel Plants: Electric Arc]
[Sec. 60.274a - Monitoring of operations.]
[From the U.S. Government Printing Office]


40PROTECTION OF ENVIRONMENT62009-07-012009-07-01falseMonitoring of operations.60.274aSec. 60.274aPROTECTION OF ENVIRONMENTENVIRONMENTAL PROTECTION AGENCY (CONTINUED)AIR PROGRAMS (CONTINUED)STANDARDS OF PERFORMANCE FOR NEW STATIONARY SOURCES--Standards of Performance for Steel Plants: Electric Arc
Sec. 60.274a  Monitoring of operations.

    (a) The owner or operator subject to the provisions of this subpart 
shall maintain records of the following information:
    (1) All data obtained under paragraph (b) of this section; and
    (2) All monthly operational status inspections performed under 
paragraph (c) of this section.
    (b) Except as provided under paragraph (e) of this section, the 
owner or operator subject to the provisions of this subpart shall check 
and record on a once-per-shift basis the furnace static pressure (if DEC 
system is in use, and a furnace static pressure gauge is installed 
according to paragraph (f) of this section) and either: check and record 
the control system fan motor amperes and damper position on a once-per-
shift basis; install, calibrate, and maintain a monitoring device that 
continuously records the volumetric flow rate through each separately 
ducted hood; or install, calibrate, and maintain a monitoring device 
that continuously records the volumetric flow rate at the control device 
inlet and check and record damper positions on a once-per-shift basis. 
The monitoring device(s) may be installed in any appropriate location in 
the exhaust duct such that reproducible flow rate monitoring will 
result. The flow rate monitoring device(s) shall have an accuracy of 
10 percent over its normal operating range and 
shall be calibrated according to the manufacturer's instructions. The 
Administrator may require the owner or operator to demonstrate the 
accuracy of the monitoring device(s) relative to Methods 1 and 2 of 
appendix A of this part.
    (c) When the owner or operator of an affected facility is required 
to demonstrate compliance with the standards under Sec. 60.272a(a)(3) 
and at any other time that the Administrator may require (under section 
114 of the CAA, as amended) either: the control system fan motor amperes 
and all damper positions, the volumetric flow rate through each 
separately ducted hood, or the volumetric flow rate at the control 
device inlet and all damper positions shall be determined during all 
periods in which a hood is operated for the purpose of capturing 
emissions from the affected facility subject to paragraph (b) of this 
section. The owner or operator may petition the Administrator for 
reestablishment of these parameters whenever the owner or operator can 
demonstrate to the Administrator's satisfaction that the affected 
facility operating conditions upon which the parameters were previously 
established are no longer applicable. The values of these parameters as 
determined during the most recent demonstration of compliance shall be 
maintained at the appropriate level for each applicable period. 
Operation at other than baseline values may be subject to the 
requirements of Sec. 60.276a(c).
    (d) Except as provided under paragraph (e) of this section, the 
owner or operator shall perform monthly operational status inspections 
of the equipment that is important to the performance of the total 
capture system (i.e., pressure sensors, dampers, and damper switches). 
This inspection shall include observations of the physical appearance of 
the equipment (e.g., presence of holes in ductwork or hoods, flow 
constrictions caused by dents or accumulated dust in ductwork, and fan 
erosion). Any deficiencies shall be noted and proper maintenance 
performed.
    (e) The owner or operator may petition the Administrator to approve 
any alternative to either the monitoring requirements specified in 
paragraph (b) of this section or the monthly operational status 
inspections specified in paragraph (d) of this section if the 
alternative will provide a continuous record of operation of each 
emission capture system.
    (f) Except as provided for under Sec. 60.273a(d), if emissions 
during any phase of the heat time are controlled by the use of a DEC 
system, the owner or operator shall install, calibrate, and maintain a 
monitoring device that allows the pressure in the free space inside the 
EAF to be monitored. The pressure shall be recorded as 15-minute 
integrated averages. The monitoring

[[Page 416]]

device may be installed in any appropriate location in the EAF or DEC 
duct prior to the introduction of ambient air such that reproducible 
results will be obtained. The pressure monitoring device shall have an 
accuracy of 5 mm of water gauge over its normal 
operating range and shall be calibrated according to the manufacturer's 
instructions.
    (g) Except as provided for under Sec. 60.273a(d), when the owner or 
operator of an EAF controlled by a DEC is required to demonstrate 
compliance with the standard under Sec. 60.272a(a)(3), and at any other 
time the Administrator may require (under section 114 of the Clean Air 
Act, as amended), the pressure in the free space inside the furnace 
shall be determined during the meltdown and refining period(s) using the 
monitoring device required under paragraph (f) of this section. The 
owner or operator may petition the Administrator for reestablishment of 
the pressure whenever the owner or operator can demonstrate to the 
Administrator's satisfaction that the EAF operating conditions upon 
which the pressures were previously established are no longer 
applicable. The pressure determined during the most recent demonstration 
of compliance shall be maintained at all times when the EAF is operating 
in a meltdown and refining period. Operation at higher pressures may be 
considered by the Administrator to be unacceptable operation and 
maintenance of the affected facility.
    (h) During any performance test required under Sec. 60.8, and for 
any report thereof required by Sec. 60.276a(f) of this subpart, or to 
determine compliance with Sec. 60.272a(a)(3) of this subpart, the owner 
or operator shall monitor the following information for all heats 
covered by the test:
    (1) Charge weights and materials, and tap weights and materials;
    (2) Heat times, including start and stop times, and a log of process 
operation, including periods of no operation during testing and the 
pressure inside an EAF when direct-shell evacuation control systems are 
used;
    (3) Control device operation log; and
    (4) Continuous opacity monitor or Method 9 data.

[49 FR 43845, Oct. 31, 1984, as amended at 64 FR 10111, Mar. 2, 1999; 65 
FR 61758, Oct. 17, 2000; 70 FR 8533, Feb. 22, 2005]