[Title 40 CFR 60.4209]
[Code of Federal Regulations (annual edition) - July 1, 2009 Edition]
[Title 40 - PROTECTION OF ENVIRONMENT]
[Chapter I - ENVIRONMENTAL PROTECTION AGENCY (CONTINUED)]
[Subchapter C - AIR PROGRAMS (CONTINUED)]
[Part 60 - STANDARDS OF PERFORMANCE FOR NEW STATIONARY SOURCES--]
[Subpart IIIi - Standards of Performance for Stationary Compression]
[Sec. 60.4209 - What are the monitoring requirements if I am an owner or]
[From the U.S. Government Printing Office]
40PROTECTION OF ENVIRONMENT62009-07-012009-07-01falseWhat are the monitoring requirements if I am an owner or60.4209Sec. 60.4209PROTECTION OF ENVIRONMENTENVIRONMENTAL PROTECTION AGENCY (CONTINUED)AIR PROGRAMS (CONTINUED)STANDARDS OF PERFORMANCE FOR NEW STATIONARY SOURCES--Standards of Performance for Stationary Compression
Sec. 60.4209 What are the monitoring requirements if I am an owner or
operator of a stationary CI internal combustion engine?
If you are an owner or operator, you must meet the monitoring
requirements of this section. In addition, you must also meet the
monitoring requirements specified in Sec. 60.4211.
(a) If you are an owner or operator of an emergency stationary CI
internal combustion engine, you must install a non-resettable hour meter
prior to startup of the engine.
(b) If you are an owner or operator of a stationary CI internal
combustion engine equipped with a diesel particulate filter to comply
with the emission standards in Sec. 60.4204, the diesel particulate
filter must be installed with a backpressure monitor that notifies the
owner or operator when the high backpressure limit of the engine is
approached.
Compliance Requirements