[Title 40 CFR 60.48Da]
[Code of Federal Regulations (annual edition) - July 1, 2009 Edition]
[Title 40 - PROTECTION OF ENVIRONMENT]
[Chapter I - ENVIRONMENTAL PROTECTION AGENCY (CONTINUED)]
[Subchapter C - AIR PROGRAMS (CONTINUED)]
[Part 60 - STANDARDS OF PERFORMANCE FOR NEW STATIONARY SOURCES--]
[Subpart Da - Standards of Performance for Electric Utility Steam]
[Sec. 60.48da - Compliance provisions.]
[From the U.S. Government Printing Office]
40PROTECTION OF ENVIRONMENT62009-07-012009-07-01falseCompliance provisions.60.48DaSec. 60.48DaPROTECTION OF ENVIRONMENTENVIRONMENTAL PROTECTION AGENCY (CONTINUED)AIR PROGRAMS (CONTINUED)STANDARDS OF PERFORMANCE FOR NEW STATIONARY SOURCES--Standards of Performance for Electric Utility Steam
Sec. 60.48Da Compliance provisions.
(a) Compliance with the PM emission limitation under Sec.
60.42Da(a)(1) constitutes compliance with the percent reduction
requirements for PM under Sec. 60.42Da(a)(2) and (3).
(b) Compliance with the NOX emission limitation under
Sec. 60.44Da(a)(1) constitutes compliance with the percent reduction
requirements under Sec. 60.44Da(a)(2).
(c) The PM emission standards under Sec. 60.42Da, the
NOX emission standards under Sec. 60.44Da, and the Hg
emission standards under Sec. 60.45Da apply at all times except during
periods of startup, shutdown, or malfunction.
(d) During emergency conditions in the principal company, an
affected facility with a malfunctioning flue gas desulfurization system
may be operated if SO2 emissions are minimized by:
(1) Operating all operable flue gas desulfurization system modules,
and bringing back into operation any malfunctioned module as soon as
repairs are completed,
(2) Bypassing flue gases around only those flue gas desulfurization
system modules that have been taken out of operation because they were
incapable of any SO2 emission reduction or which would have
suffered significant physical damage if they had remained in operation,
and
(3) Designing, constructing, and operating a spare flue gas
desulfurization system module for an affected facility larger than 365
MW (1,250 MMBtu/hr) heat input (approximately 125 MW electrical output
capacity). The Administrator may at his discretion require the owner or
operator within 60 days of notification to demonstrate spare module
capability. To demonstrate this capability, the owner or operator must
demonstrate compliance with the appropriate requirements under paragraph
under Sec. 60.43Da(a), (b), (d), (e), and (h) for any period of
operation lasting from 24 hours to 30 days when:
(i) Any one flue gas desulfurization module is not operated,
(ii) The affected facility is operating at the maximum heat input
rate,
(iii) The fuel fired during the 24-hour to 30-day period is
representative of the type and average sulfur content of fuel used over
a typical 30-day period, and
(iv) The owner or operator has given the Administrator at least 30
days notice of the date and period of time over which the demonstration
will be performed.
[[Page 162]]
(e) After the initial performance test required under Sec. 60.8,
compliance with the SO2 emission limitations and percentage
reduction requirements under Sec. 60.43Da and the NOX
emission limitations under Sec. 60.44Da is based on the average
emission rate for 30 successive boiler operating days. A separate
performance test is completed at the end of each boiler operating day
after the initial performance test, and a new 30 day average emission
rate for both SO2 and NOX and a new percent
reduction for SO2 are calculated to show compliance with the
standards.
(f) For the initial performance test required under Sec. 60.8,
compliance with the SO2 emission limitations and percent
reduction requirements under Sec. 60.43Da and the NOX
emission limitation under Sec. 60.44Da is based on the average emission
rates for SO2, NOX, and percent reduction for
SO2 for the first 30 successive boiler operating days. The
initial performance test is the only test in which at least 30 days
prior notice is required unless otherwise specified by the
Administrator. The initial performance test is to be scheduled so that
the first boiler operating day of the 30 successive boiler operating
days is completed within 60 days after achieving the maximum production
rate at which the affected facility will be operated, but not later than
180 days after initial startup of the facility.
(g) The owner or operator of an affected facility subject to
emission limitations in this subpart shall determine compliance as
follows:
(1) Compliance with applicable 30-day rolling average SO2
and NOX emission limitations is determined by calculating the
arithmetic average of all hourly emission rates for SO2 and
NOX for the 30 successive boiler operating days, except for
data obtained during startup, shutdown, malfunction (NOX
only), or emergency conditions (SO2 only).
(2) Compliance with applicable SO2 percentage reduction
requirements is determined based on the average inlet and outlet
SO2 emission rates for the 30 successive boiler operating
days.
(3) Compliance with applicable daily average PM emission limitations
is determined by calculating the arithmetic average of all hourly
emission rates for PM each boiler operating day, except for data
obtained during startup, shutdown, and malfunction. Averages are only
calculated for boiler operating days that have valid data for at least
18 hours of unit operation during which the standard applies. Instead,
all of the valid hourly emission rates of the operating day(s) not
meeting the minimum 18 hours valid data daily average requirement are
averaged with all of the valid hourly emission rates of the next boiler
operating day with 18 hours or more of valid PM CEMS data to determine
compliance.
(h) If an owner or operator has not obtained the minimum quantity of
emission data as required under Sec. 60.49Da of this subpart,
compliance of the affected facility with the emission requirements under
Sec. Sec. 60.43Da and 60.44Da of this subpart for the day on which the
30-day period ends may be determined by the Administrator by following
the applicable procedures in section 7 of Method 19 of appendix A of
this part.
(i) Compliance provisions for sources subject to Sec.
60.44Da(d)(1), (e)(1), (e)(2)(i), (e)(3)(i), or (f). The owner or
operator of an affected facility subject to Sec. 60.44Da(d)(1), (e)(1),
(e)(2)(i), (e)(3)(i), or (f) shall calculate NOX emissions as
1.194 x 10-\7\ lb/scf-ppm times the average hourly
NOX output concentration in ppm (measured according to the
provisions of Sec. 60.49Da(c)), times the average hourly flow rate
(measured in scfh, according to the provisions of Sec. 60.49Da(l) or
Sec. 60.49Da(m)), divided by the average hourly gross energy output
(measured according to the provisions of Sec. 60.49Da(k)).
Alternatively, for oil-fired and gas-fired units, NOX
emissions may be calculated by multiplying the hourly NOX
emission rate in lb/MMBtu (measured by the CEMS required under
Sec. Sec. 60.49Da(c) and (d)), by the hourly heat input rate (measured
according to the provisions of Sec. 60.49Da(n)), and dividing the
result by the average gross energy output (measured according to the
provisions of Sec. 60.49Da(k)).
(j) Compliance provisions for duct burners subject to Sec.
60.44Da(a)(1). To determine compliance with the emissions limits for
NOX required by Sec. 60.44Da(a) for duct burners used in
combined cycle systems, either of the procedures
[[Page 163]]
described in paragraph (j)(1) or (2) of this section may be used:
(1) The owner or operator of an affected duct burner shall conduct
the performance test required under Sec. 60.8 using the appropriate
methods in appendix A of this part. Compliance with the emissions limits
under Sec. 60.44Da(a)(1) is determined on the average of three (nominal
1-hour) runs for the initial and subsequent performance tests. During
the performance test, one sampling site shall be located in the exhaust
of the turbine prior to the duct burner. A second sampling site shall be
located at the outlet from the heat recovery steam generating unit.
Measurements shall be taken at both sampling sites during the
performance test; or
(2) The owner or operator of an affected duct burner may elect to
determine compliance by using the CEMS specified under Sec. 60.49Da for
measuring NOX and oxygen (O2) (or carbon dioxide
(CO2)) and meet the requirements of Sec. 60.49Da.
Alternatively, data from a NOX emission rate (i.e.,
NOX-diluent) CEMS certified according to the provisions of
Sec. 75.20(c) of this chapter and appendix A to part 75 of this
chapter, and meeting the quality assurance requirements of Sec. 75.21
of this chapter and appendix B to part 75 of this chapter, may be used,
with the following caveats. Data used to meet the requirements of Sec.
60.51Da shall not include substitute data values derived from the
missing data procedures in subpart D of part 75 of this chapter, nor
shall the data have been bias adjusted according to the procedures of
part 75 of this chapter. The sampling site shall be located at the
outlet from the steam generating unit. The NOX emission rate
at the outlet from the steam generating unit shall constitute the
NOX emission rate from the duct burner of the combined cycle
system.
(k) Compliance provisions for duct burners subject to Sec.
60.44Da(d)(1) or (e)(1). To determine compliance with the emission
limitation for NOX required by Sec. 60.44Da(d)(1) or (e)(1)
for duct burners used in combined cycle systems, either of the
procedures described in paragraphs (k)(1) and (2) of this section may be
used:
(1) The owner or operator of an affected duct burner used in
combined cycle systems shall determine compliance with the applicable
NOX emission limitation in Sec. 60.44Da(d)(1) or (e)(1) as
follows:
(i) The emission rate (E) of NOX shall be computed using
Equation 2 in this section:
[GRAPHIC] [TIFF OMITTED] TR13JN07.012
Where:
E = Emission rate of NOX from the duct burner, ng/J (lb/MWh)
gross output;
Csg = Average hourly concentration of NOX exiting
the steam generating unit, ng/dscm (lb/dscf);
Cte = Average hourly concentration of NOX in the
turbine exhaust upstream from duct burner, ng/dscm (lb/dscf);
Qsg = Average hourly volumetric flow rate of exhaust gas from
steam generating unit, dscm/hr (dscf/hr);
Qte = Average hourly volumetric flow rate of exhaust gas from
combustion turbine, dscm/hr (dscf/hr);
Osg = Average hourly gross energy output from steam
generating unit, J (MWh); and
h = Average hourly fraction of the total heat input to the steam
generating unit derived from the combustion of fuel in the affected duct
burner.
(ii) Method 7E of appendix A of this part shall be used to determine
the NOX concentrations (Csg and Cte).
Method 2, 2F or 2G of appendix A of this part, as appropriate, shall be
used to determine the volumetric flow rates (Qsg and
Qte) of the exhaust gases. The volumetric flow rate
measurements shall be taken at the same time as the concentration
measurements.
(iii) The owner or operator shall develop, demonstrate, and provide
information satisfactory to the Administrator to determine the average
hourly gross energy output from the steam generating unit, and the
average hourly percentage of the total heat input to the steam
generating unit derived from the combustion of fuel in the affected duct
burner.
(iv) Compliance with the applicable NOX emission
limitation in Sec. 60.44Da(d)(1) or (e)(1) is determined by the three-
run average (nominal 1-hour runs) for the initial and subsequent
performance tests.
[[Page 164]]
(2) The owner or operator of an affected duct burner used in a
combined cycle system may elect to determine compliance with the
applicable NOX emission limitation in Sec. 60.44Da(d)(1) or
(e)(1) on a 30-day rolling average basis as indicated in paragraphs
(k)(2)(i) through (iv) of this section.
(i) The emission rate (E) of NOX shall be computed using
Equation 3 in this section:
[GRAPHIC] [TIFF OMITTED] TR13JN07.013
Where:
E = Emission rate of NOX from the duct burner, ng/J (lb/MWh)
gross output;
Csg = Average hourly concentration of NOX exiting
the steam generating unit, ng/dscm (lb/dscf);
Qsg = Average hourly volumetric flow rate of exhaust gas from
steam generating unit, dscm/hr (dscf/hr); and
Occ = Average hourly gross energy output from entire combined
cycle unit, J (MWh).
(ii) The CEMS specified under Sec. 60.49Da for measuring
NOX and O2 (or CO2) shall be used to
determine the average hourly NOX concentrations
(Csg). The continuous flow monitoring system specified in
Sec. 60.49Da(l) or Sec. 60.49Da(m) shall be used to determine the
volumetric flow rate (Qsg) of the exhaust gas. If the option
to use the flow monitoring system in Sec. 60.49Da(m) is selected, the
flow rate data used to meet the requirements of Sec. 60.51Da shall not
include substitute data values derived from the missing data procedures
in subpart D of part 75 of this chapter, nor shall the data have been
bias adjusted according to the procedures of part 75 of this chapter.
The sampling site shall be located at the outlet from the steam
generating unit.
(iii) The continuous monitoring system specified under Sec.
60.49Da(k) for measuring and determining gross energy output shall be
used to determine the average hourly gross energy output from the entire
combined cycle unit (Occ), which is the combined output from
the combustion turbine and the steam generating unit.
(iv) The owner or operator may, in lieu of installing, operating,
and recording data from the continuous flow monitoring system specified
in Sec. 60.49Da(l), determine the mass rate (lb/hr) of NOX
emissions by installing, operating, and maintaining continuous fuel
flowmeters following the appropriate measurements procedures specified
in appendix D of part 75 of this chapter. If this compliance option is
selected, the emission rate (E) of NOX shall be computed
using Equation 4 in this section:
[GRAPHIC] [TIFF OMITTED] TR13JN07.014
Where:
E = Emission rate of NOX from the duct burner, ng/J (lb/MWh)
gross output;
ERsg = Average hourly emission rate of NOX exiting
the steam generating unit heat input calculated using appropriate F
factor as described in Method 19 of appendix A of this part, ng/J (lb/
MMBtu);
Hcc = Average hourly heat input rate of entire combined cycle
unit, J/hr (MMBtu/hr); and
Occ = Average hourly gross energy output from entire combined
cycle unit, J (MWh).
(3) When an affected duct burner steam generating unit utilizes a
common steam turbine with one or more affected duct burner steam
generating units, the owner or operator shall either:
(i) Determine compliance with the applicable NOX
emissions limits by measuring the emissions combined with the emissions
from the other unit(s) utilizing the common steam turbine; or
(ii) Develop, demonstrate, and provide information satisfactory to
the Administrator on methods for apportioning the combined gross energy
output from the steam turbine for each of the affected duct burners. The
Administrator may approve such demonstrated substitute methods for
apportioning the combined gross energy output measured at the steam
turbine whenever the demonstration ensures accurate estimation of
emissions regulated under this part.
(l) Compliance provisions for sources subject to Sec. 60.45Da. The
owner or operator of an affected facility subject to Sec. 60.45Da (new
sources constructed or reconstructed after January 30, 2004) shall
calculate the Hg emission rate (lb/MWh) for each calendar month of
[[Page 165]]
the year, using hourly Hg concentrations measured according to the
provisions of Sec. 60.49Da(p) in conjunction with hourly stack gas
volumetric flow rates measured according to the provisions of Sec.
60.49Da(l) or (m), and hourly gross electrical outputs, determined
according to the provisions in Sec. 60.49Da(k). Compliance with the
applicable standard under Sec. 60.45Da is determined on a 12-month
rolling average basis.
(m) Compliance provisions for sources subject to Sec.
60.43Da(i)(1)(i), (i)(2)(i), (i)(3)(i), (j)(1)(i), (j)(2)(i), or
(j)(3)(i). The owner or operator of an affected facility subject to
Sec. 60.43Da(i)(1)(i), (i)(2)(i), (i)(3)(i), (j)(1)(i), (j)(2)(i), or
(j)(3)(i) shall calculate SO2 emissions as 1.660 x
10-7 lb/scf-ppm times the average hourly SO2
output concentration in ppm (measured according to the provisions of
Sec. 60.49Da(b)), times the average hourly flow rate (measured
according to the provisions of Sec. 60.49Da(l) or Sec. 60.49Da(m)),
divided by the average hourly gross energy output (measured according to
the provisions of Sec. 60.49Da(k)). Alternatively, for oil-fired and
gas-fired units, SO2 emissions may be calculated by
multiplying the hourly SO2 emission rate (in lb/MMBtu),
measured by the CEMS required under Sec. 60.49Da, by the hourly heat
input rate (measured according to the provisions of Sec. 60.49Da(n)),
and dividing the result by the average gross energy output (measured
according to the provisions of Sec. 60.49Da(k)).
(n) Compliance provisions for sources subject to Sec.
60.42Da(c)(1). The owner or operator of an affected facility subject to
Sec. 60.42Da(c)(1) shall calculate PM emissions by multiplying the
average hourly PM output concentration (measured according to the
provisions of Sec. 60.49Da(t)), by the average hourly flow rate
(measured according to the provisions of Sec. 60.49Da(l) or Sec.
60.49Da(m)), and divided by the average hourly gross energy output
(measured according to the provisions of Sec. 60.49Da(k)). Compliance
with the emission limit is determined by calculating the arithmetic
average of the hourly emission rates computed for each boiler operating
day.
(o) Compliance provisions for sources subject to Sec. 60.42Da(c)(2)
or (d). Except as provided for in paragraph (p) of this section, the
owner or operator of an affected facility for which construction,
reconstruction, or modification commenced after February 28, 2005, shall
demonstrate compliance with each applicable emission limit according to
the requirements in paragraphs (o)(1) through (o)(5) of this section.
(1) You must conduct a performance test to demonstrate initial
compliance with the applicable PM emissions limit in Sec. 60.42Da(c)(2)
or (d) by the applicable date specified in Sec. 60.8(a). Thereafter,
you must conduct each subsequent performance test within 12 calendar
months following the date the previous performance test was required to
be conducted. You must conduct each performance test according to the
requirements in Sec. 60.8 using the test methods and procedures in
Sec. 60.50Da. The owner or operator of an affected facility that has
not operated for 60 consecutive calendar days prior to the date that the
subsequent performance test would have been required had the unit been
operating is not required to perform the subsequent performance test
until 30 calendar days after the next boiler operating day. Requests for
additional 30 day extensions shall be granted by the relevant air
division or office director of the appropriate Regional Office of the
U.S. EPA.
(2) You must monitor the performance of each electrostatic
precipitator or fabric filter (baghouse) operated to comply with the
applicable PM emissions limit in Sec. 60.42Da(c)(2) or (d) using a
continuous opacity monitoring system (COMS) according to the
requirements in paragraphs (o)(2)(i) through (vi) unless you elect to
comply with one of the alternatives provided in paragraphs (o)(3) and
(o)(4) of this section, as applicable to your control device.
(i) Each COMS must meet Performance Specification 1 in 40 CFR part
60, appendix B.
(ii) You must comply with the quality assurance requirements in
paragraphs (o)(2)(ii)(A) through (E) of this section.
(A) You must automatically (intrinsic to the opacity monitor) check
the zero and upscale (span) calibration drifts at least once daily. For
a particular COMS, the acceptable range of
[[Page 166]]
zero and upscale calibration materials is as defined in the applicable
version of Performance Specification 1 in 40 CFR part 60, appendix B.
(B) You must adjust the zero and span whenever the 24-hour zero
drift or 24-hour span drift exceeds 4 percent opacity. The COMS must
allow for the amount of excess zero and span drift measured at the 24-
hour interval checks to be recorded and quantified. The optical surfaces
exposed to the effluent gases must be cleaned prior to performing the
zero and span drift adjustments, except for systems using automatic zero
adjustments. For systems using automatic zero adjustments, the optical
surfaces must be cleaned when the cumulative automatic zero compensation
exceeds 4 percent opacity.
(C) You must apply a method for producing a simulated zero opacity
condition and an upscale (span) opacity condition using a certified
neutral density filter or other related technique to produce a known
obscuration of the light beam. All procedures applied must provide a
system check of the analyzer internal optical surfaces and all
electronic circuitry including the lamp and photodetector assembly.
(D) Except during periods of system breakdowns, repairs, calibration
checks, and zero and span adjustments, the COMS must be in continuous
operation and must complete a minimum of one cycle of sampling and
analyzing for each successive 10 second period and one cycle of data
recording for each successive 6-minute period.
(E) You must reduce all data from the COMS to 6-minute averages.
Six-minute opacity averages must be calculated from 36 or more data
points equally spaced over each 6-minute period. Data recorded during
periods of system breakdowns, repairs, calibration checks, and zero and
span adjustments must not be included in the data averages. An
arithmetic or integrated average of all data may be used.
(iii) During each performance test conducted according to paragraph
(o)(1) of this section, you must establish an opacity baseline level.
The value of the opacity baseline level is determined by averaging all
of the 6-minute average opacity values (reported to the nearest 0.1
percent opacity) from the COMS measurements recorded during each of the
test run intervals conducted for the performance test, and then adding
2.5 percent opacity to your calculated average opacity value for all of
the test runs. If your opacity baseline level is less than 5.0 percent,
then the opacity baseline level is set at 5.0 percent.
(iv) You must evaluate the preceding 24-hour average opacity level
measured by the COMS each boiler operating day excluding periods of
affected facility startup, shutdown, or malfunction. If the measured 24-
hour average opacity emission level is greater than the baseline opacity
level determined in paragraph (o)(2)(iii) of this section, you must
initiate investigation of the relevant equipment and control systems
within 24 hours of the first discovery of the high opacity incident and
take the appropriate corrective action as soon as practicable to adjust
control settings or repair equipment to reduce the measured 24-hour
average opacity to a level below the baseline opacity level. In cases
when a wet scrubber is used in combination with another PM control
device that serves as the primary PM control device, the wet scrubber
must be maintained and operated.
(v) You must record the opacity measurements, calculations
performed, and any corrective actions taken. The record of corrective
action taken must include the date and time during which the measured
24-hour average opacity was greater than baseline opacity level, and the
date, time, and description of the corrective action.
(vi) If the measured 24-hour average opacity for your affected
facility remains at a level greater than the opacity baseline level
after 7 boiler operating days, then you must conduct a new PM
performance test according to paragraph (o)(1) of this section and
establish a new opacity baseline value according to paragraph (o)(2) of
this section. This new performance test must be conducted within 60 days
of the date that the measured 24-hour average opacity was first
determined to exceed the baseline opacity level unless a waiver is
granted by the permitting authority.
[[Page 167]]
(3) As an alternative to complying with the requirements of
paragraph (o)(2) of this section, an owner or operator may elect to
monitor the performance of an electrostatic precipitator (ESP) operated
to comply with the applicable PM emissions limit in Sec. 60.42Da(c)(2)
or (d) using an ESP predictive model developed in accordance with the
requirements in paragraphs (o)(3)(i) through (v) of this section.
(i) You must calibrate the ESP predictive model with each PM control
device used to comply with the applicable PM emissions limit in Sec.
60.42Da(c)(2) or (d) operating under normal conditions. In cases when a
wet scrubber is used in combination with an ESP to comply with the PM
emissions limit, the wet scrubber must be maintained and operated.
(ii) You must develop a site-specific monitoring plan that includes
a description of the ESP predictive model used, the model input
parameters, and the procedures and criteria for establishing monitoring
parameter baseline levels indicative of compliance with the PM emissions
limit. You must submit the site-specific monitoring plan for approval by
the permitting authority. For reference purposes in preparing the
monitoring plan, see the OAQPS ``Compliance Assurance Monitoring (CAM)
Protocol for an Electrostatic Precipitator (ESP) Controlling Particulate
Matter (PM) Emissions from a Coal-Fired Boiler.'' This document is
available from the U.S. Environmental Protection Agency (U.S. EPA);
Office of Air Quality Planning and Standards; Sector Policies and
Programs Division; Measurement Policy Group (D243-02), Research Triangle
Park, NC 27711. This document is also available on the Technology
Transfer Network (TTN) under Emission Measurement Center Continuous
Emission Monitoring.
(iii) You must run the ESP predictive model using the applicable
input data each boiler operating day and evaluate the model output for
the preceding boiler operating day excluding periods of affected
facility startup, shutdown, or malfunction. If the values for one or
more of the model parameters exceed the applicable baseline levels
determined according to your approved site-specific monitoring plan, you
must initiate investigation of the relevant equipment and control
systems within 24 hours of the first discovery of a model parameter
deviation and, take the appropriate corrective action as soon as
practicable to adjust control settings or repair equipment to return the
model output to within the applicable baseline levels.
(iv) You must record the ESP predictive model inputs and outputs and
any corrective actions taken. The record of corrective action taken must
include the date and time during which the model output values exceeded
the applicable baseline levels, and the date, time, and description of
the corrective action.
(v) If after 7 consecutive days a model parameter continues to
exceed the applicable baseline level, then you must conduct a new PM
performance test according to paragraph (o)(1) of this section. This new
performance test must be conducted within 60 calendar days of the date
that the model parameter was first determined to exceed its baseline
level unless a waiver is granted by the permitting authority.
(4) As an alternative to complying with the requirements of
paragraph (o)(2) of this section, an owner or operator may elect to
monitor the performance of a fabric filter (baghouse) operated to comply
with the applicable PM emissions limit in Sec. 60.42Da(c)(2) or (d) by
using a bag leak detection system according to the requirements in
paragraphs (o)(4)(i) through (v) of this section.
(i) Each bag leak detection system must meet the specifications and
requirements in paragraphs (o)(4)(i)(A) through (H) of this section.
(A) The bag leak detection system must be certified by the
manufacturer to be capable of detecting PM emissions at concentrations
of 1 milligram per actual cubic meter (0.00044 grains per actual cubic
foot) or less.
(B) The bag leak detection system sensor must provide output of
relative PM loadings. The owner or operator must continuously record the
output from the bag leak detection system using electronic or other
means (e.g., using a strip chart recorder or a data logger.)
[[Page 168]]
(C) The bag leak detection system must be equipped with an alarm
system that will react when the system detects an increase in relative
particulate loading over the alarm set point established according to
paragraph (o)(4)(i)(D) of this section, and the alarm must be located
such that it can be noticed by the appropriate plant personnel.
(D) In the initial adjustment of the bag leak detection system, you
must establish, at a minimum, the baseline output by adjusting the
sensitivity (range) and the averaging period of the device, the alarm
set points, and the alarm delay time.
(E) Following initial adjustment, you must not adjust the averaging
period, alarm set point, or alarm delay time without approval from the
permitting authority except as provided in paragraph (d)(1)(vi) of this
section.
(F) Once per quarter, you may adjust the sensitivity of the bag leak
detection system to account for seasonal effects, including temperature
and humidity, according to the procedures identified in the site-
specific monitoring plan required by paragraph (o)(4)(ii) of this
section.
(G) You must install the bag leak detection sensor downstream of the
fabric filter and upstream of any wet scrubber.
(H) Where multiple detectors are required, the system's
instrumentation and alarm may be shared among detectors.
(ii) You must develop and submit to the permitting authority for
approval a site-specific monitoring plan for each bag leak detection
system. You must operate and maintain the bag leak detection system
according to the site-specific monitoring plan at all times. Each
monitoring plan must describe the items in paragraphs (o)(4)(ii)(A)
through (F) of this section.
(A) Installation of the bag leak detection system;
(B) Initial and periodic adjustment of the bag leak detection
system, including how the alarm set-point will be established;
(C) Operation of the bag leak detection system, including quality
assurance procedures;
(D) How the bag leak detection system will be maintained, including
a routine maintenance schedule and spare parts inventory list;
(E) How the bag leak detection system output will be recorded and
stored; and
(F) Corrective action procedures as specified in paragraph
(o)(4)(iii) of this section. In approving the site-specific monitoring
plan, the permitting authority may allow owners and operators more than
3 hours to alleviate a specific condition that causes an alarm if the
owner or operator identifies in the monitoring plan this specific
condition as one that could lead to an alarm, adequately explains why it
is not feasible to alleviate this condition within 3 hours of the time
the alarm occurs, and demonstrates that the requested time will ensure
alleviation of this condition as expeditiously as practicable.
(iii) For each bag leak detection system, you must initiate
procedures to determine the cause of every alarm within 1 hour of the
alarm. Except as provided in paragraph (o)(4)(ii)(F) of this section,
you must alleviate the cause of the alarm within 3 hours of the alarm by
taking whatever corrective action(s) are necessary. Corrective actions
may include, but are not limited to the following:
(A) Inspecting the fabric filter for air leaks, torn or broken bags
or filter media, or any other condition that may cause an increase in
particulate emissions;
(B) Sealing off defective bags or filter media;
(C) Replacing defective bags or filter media or otherwise repairing
the control device;
(D) Sealing off a defective fabric filter compartment;
(E) Cleaning the bag leak detection system probe or otherwise
repairing the bag leak detection system; or
(F) Shutting down the process producing the particulate emissions.
(iv) You must maintain records of the information specified in
paragraphs (o)(4)(iv)(A) through (C) of this section for each bag leak
detection system.
(A) Records of the bag leak detection system output;
[[Page 169]]
(B) Records of bag leak detection system adjustments, including the
date and time of the adjustment, the initial bag leak detection system
settings, and the final bag leak detection system settings; and
(C) The date and time of all bag leak detection system alarms, the
time that procedures to determine the cause of the alarm were initiated,
if procedures were initiated within 1 hour of the alarm, the cause of
the alarm, an explanation of the actions taken, the date and time the
cause of the alarm was alleviated, and if the alarm was alleviated
within 3 hours of the alarm.
(v) If after any period composed of 30 boiler operating days during
which the alarm rate exceeds 5 percent of the process operating time
(excluding control device or process startup, shutdown, and
malfunction), then you must conduct a new PM performance test according
to paragraph (o)(1) of this section. This new performance test must be
conducted within 60 calendar days of the date that the alarm rate was
first determined to exceed 5 percent limit unless a waiver is granted by
the permitting authority.
(5) An owner or operator of a modified affected facility electing to
meet the emission limitations in Sec. 60.42Da(d) shall determine the
percent reduction in PM by using the emission rate for PM determined by
the performance test conducted according to the requirements in
paragraph (o)(1) of this section and the ash content on a mass basis of
the fuel burned during each performance test run as determined by
analysis of the fuel as fired.
(p) As an alternative to meeting the compliance provisions specified
in paragraph (o) of this section, an owner or operator may elect to
install, evaluate, maintain, and operate a CEMS measuring PM emissions
discharged from the affected facility to the atmosphere and record the
output of the system as specified in paragraphs (p)(1) through (p)(8) of
this section.
(1) The owner or operator shall submit a written notification to the
Administrator of intent to demonstrate compliance with this subpart by
using a CEMS measuring PM. This notification shall be sent at least 30
calendar days before the initial startup of the monitor for compliance
determination purposes. The owner or operator may discontinue operation
of the monitor and instead return to demonstration of compliance with
this subpart according to the requirements in paragraph (o) of this
section by submitting written notification to the Administrator of such
intent at least 30 calendar days before shutdown of the monitor for
compliance determination purposes.
(2) Each CEMS shall be installed, evaluated, operated, and
maintained according to the requirements in Sec. 60.49Da(v).
(3) The initial performance evaluation shall be completed no later
than 180 days after the date of initial startup of the affected
facility, as specified under Sec. 60.8 of subpart A of this part or
within 180 days of the date of notification to the Administrator
required under paragraph (p)(1) of this section, whichever is later.
(4) Compliance with the applicable emissions limit shall be
determined based on the 24-hour daily (block) average of the hourly
arithmetic average emissions concentrations using the continuous
monitoring system outlet data. The 24-hour block arithmetic average
emission concentration shall be calculated using EPA Reference Method 19
of appendix A of this part, section 4.1.
(5) At a minimum, valid CEMS hourly averages shall be obtained for
75 percent of all operating hours on a 30-day rolling average basis.
Beginning on January 1, 2012, valid CEMS hourly averages shall be
obtained for 90 percent of all operating hours on a 30-day rolling
average basis.
(i) At least two data points per hour shall be used to calculate
each 1-hour arithmetic average.
(ii) [Reserved]
(6) The 1-hour arithmetic averages required shall be expressed in
ng/J, MMBtu/hr, or lb/MWh and shall be used to calculate the boiler
operating day daily arithmetic average emission concentrations. The 1-
hour arithmetic averages shall be calculated using the data points
required under Sec. 60.13(e)(2) of subpart A of this part.
(7) All valid CEMS data shall be used in calculating average
emission concentrations even if the minimum
[[Page 170]]
CEMS data requirements of paragraph (j)(5) of this section are not met.
(8) When PM emissions data are not obtained because of CEMS
breakdowns, repairs, calibration checks, and zero and span adjustments,
emissions data shall be obtained by using other monitoring systems as
approved by the Administrator or EPA Reference Method 19 of appendix A
of this part to provide, as necessary, valid emissions data for a
minimum of 90 percent (only 75 percent is required prior to January 1,
2012) of all operating hours per 30-day rolling average.
(q) Compliance provisions for sources subject to Sec. 60.42Da(b).
An owner or operator of an affected facility subject to the opacity
standard in Sec. 60.42Da(b) shall monitor the opacity of emissions
discharged from the affected facility to the atmosphere according to the
requirements in Sec. 60.49Da(a), as applicable to the affected
facility.
[72 FR 32722, June 13, 2007, as amended at 74 FR 5079, Jan. 28, 2009]