[Federal Register Volume 90, Number 82 (Wednesday, April 30, 2025)]
[Proposed Rules]
[Pages 17895-17908]
From the Federal Register Online via the Government Publishing Office [www.gpo.gov]
[FR Doc No: 2025-07351]


========================================================================
Proposed Rules
                                                Federal Register
________________________________________________________________________

This section of the FEDERAL REGISTER contains notices to the public of 
the proposed issuance of rules and regulations. The purpose of these 
notices is to give interested persons an opportunity to participate in 
the rule making prior to the adoption of the final rules.

========================================================================


Federal Register / Vol. 90, No. 82 / Wednesday, April 30, 2025 / 
Proposed Rules

[[Page 17895]]



DEPARTMENT OF ENERGY

10 CFR Parts 429 and 430

[EERE-2024-BT-TP-0011]


Energy Conservation Program: Notification of Petition for 
Rulemaking

AGENCY: Office of Energy Efficiency and Renewable Energy, Department of 
Energy.

ACTION: Notification of petition for rulemaking; request for comment.

-----------------------------------------------------------------------

SUMMARY: On September 11, 2024, the Department of Energy (``DOE'') 
received a petition from Dyson Inc. for DOE to revoke the procedures by 
which manufacturers must measure and represent to consumers the 
effective room size coverage and integrated energy factor of their air 
cleaner products. If the provisions are not revoked, Dyson Inc. 
requested that DOE stay enforcement of these provisions pending a new 
notice and comment period regarding potential amendments to these 
provisions. DOE is not revoking or staying enforcement of the test 
procedure and representations provisions raised in Dyson's petition at 
this time. Through this notification, DOE is seeking views on whether 
it should grant the petition and undertake a rulemaking to consider the 
proposal contained in the petition, as well as any data or information 
that could be used in DOE's determination whether to grant the 
petition.

DATES: Written comments and information are requested and will be 
accepted on or before May 30, 2025.

ADDRESSES: Interested persons are encouraged to submit comments using 
the Federal eRulemaking Portal at www.regulations.gov under docket 
number EERE-2024-BT-TP-0011. Follow the instructions for submitting 
comments. Alternatively, interested persons may submit comments, 
identified by docket number EERE-2024-BT-TP-0011, by any of the 
following methods:
    Email: AirCleanersPetition2024TP0011@ee.doe.gov. Include the docket 
number and/or RIN in the subject line of the message.
    Postal Mail: Appliance and Equipment Standards Program, U.S. 
Department of Energy, Building Technologies Office, Mailstop EE-5B, 
1000 Independence Avenue SW, Washington, DC 20585-0121. If possible, 
please submit all items on a compact disc (``CD''), in which case it is 
not necessary to include printed copies.
    Hand Delivery/Courier: Appliance and Equipment Standards Program, 
U.S. Department of Energy, Building Technologies Office, 1000 
Independence Avenue SW, Washington, DC 20585-0121. Telephone: (202) 
287-1445. If possible, please submit all items on a CD, in which case 
it is not necessary to include printed copies.
    No telefacsimiles (``faxes'') will be accepted. For detailed 
instructions on submitting comments and additional information on this 
process, see the SUPPLEMENTARY INFORMATION section of this document.
    Docket: The docket for this activity, which includes Federal 
Register notices, public meeting attendee lists and transcripts (if a 
public meeting is held), comments, and other supporting documents/
materials, is available for review at www.regulations.gov. All 
documents in the docket are listed in the www.regulations.gov index. 
However, not all documents listed in the index may be publicly 
available, such as information that is exempt from public disclosure.
    The docket web page can be found at www.regulations.gov/docket/EERE-2024-BT-TP-0011. The docket web page contains instructions on how 
to access all documents, including public comments, in the docket.

FOR FURTHER INFORMATION CONTACT: 
    Dr. Carl Shapiro, U.S. Department of Energy, Office of Energy 
Efficiency and Renewable Energy, Building Technologies Office, Mailstop 
EE-5B, 1000 Independence Avenue SW, Washington, DC 20585-0121. 
Telephone: (240) 315-4339. Email: 
ApplianceStandardsQuestions@ee.doe.gov.
    Mr. Uchechukwu ``Emeka'' Eze, U.S. Department of Energy, Office of 
the General Counsel, Mail Stop GC-33, Forrestal Building, 1000 
Independence Avenue SW, Washington, DC 20585-0103. Telephone: (202) 
586-4798. Email: uchechukwu.eze@hq.doe.gov.

SUPPLEMENTARY INFORMATION: The Administrative Procedure Act (``APA''), 
5 U.S.C. 551 et seq., provides among other things, that ``[e]ach agency 
shall give an interested person the right to petition for the issuance, 
amendment, or repeal of a rule.'' (5 U.S.C. 553(e)) The Energy Policy 
and Conservation Act, as amended (``EPCA''), also specifically permits 
test procedures petitions. (See, 42 U.S.C. 6293(b)(2)) \1\ If the 
Secretary determines, on his own behalf or in response to a petition by 
any interested person, that a test procedure should be prescribed or 
amended, the Secretary shall promptly publish in the Federal Register 
proposed test procedures and afford interested persons an opportunity 
to present oral and written data, views, and arguments with respect to 
such procedures. The comment period shall not be less than 60 days and 
may be extended for good cause shown to not more than 270 days. In 
prescribing or amending a test procedure, the Secretary shall take into 
account such information as the Secretary determines relevant to such 
procedure, including technological developments relating to energy use 
or energy efficiency of the type (or class) of covered products 
involved. (42 U.S.C. 6293(b)(2)) When DOE determines that test 
procedure revisions are not appropriate, DOE's practice is to publish 
its determination not to amend the test procedures.
---------------------------------------------------------------------------

    \1\ All references to EPCA in this document refer to the statute 
as amended through the Energy Act of 2020, Public Law 116-260 (Dec. 
27, 2020), which reflects the last statutory amendments that impact 
Parts A and A-1 of EPCA.
---------------------------------------------------------------------------

    DOE received a petition from Dyson Inc. (``Dyson'') as described in 
this document and set forth verbatim below,\2\ requesting that DOE 
amend its regulations to revoke the following regulatory text from the 
Code of Federal Regulations (``CFR''): (1) 10 CFR 429.68(a)(4), which 
specifies that any represented value of the effective room size of an 
air cleaner basic model must be calculated as the product of 1.55 and 
the represented smoke clean air delivery rate (``CADR'') value of the 
basic model; and, (2) 10 CFR 430.23(hh)(4), which specifies that the 
annual energy consumption and integrated energy factor (``IEF'') of a 
conventional room air

[[Page 17896]]

cleaner is measured in accordance with section 7 of 10 CFR part 430, 
subpart B, appendix FF (``appendix FF''). In its petition, Dyson also 
requests that if DOE does not revoke the provisions as requested in the 
petition, that DOE stay enforcement of those provisions pending a 
period of notice and comment to consider further changes to the test 
procedure.
---------------------------------------------------------------------------

    \2\ Dyson's petition for rulemaking is available in the docket 
at www.regulations.gov/document/EERE-2024-BT-TP-0011-0001.
---------------------------------------------------------------------------

    In a final rule published on March 6, 2023 (88 FR 14014), DOE 
established the air cleaners test procedure at appendix FF and 10 CFR 
430.23(hh) and sampling and representation requirements at 10 CFR 
429.68. These test procedure requirements were established through a 
rulemaking process that included a notice of proposed rulemaking 
(``NOPR'') published on October 18, 2022. 87 FR 63324. Following 
publication of the NOPR, on August 23, 2022, DOE received a letter 
titled ``Joint Statement of Joint Stakeholder Proposal on Recommended 
Energy Conservation Standards and Test Procedure for Consumer Room Air 
Cleaners'' (hereafter referred to as the ``Joint Proposal'') \3\ 
submitted by the American Council for an Energy-Efficient Economy, 
Appliance Standards Awareness Project, Association of Home Appliance 
Manufacturers (``AHAM''),\4\ Consumer Federation of America, Natural 
Resources Defense Council, New York State Energy Research and 
Development Authority, and Pacific Gas and Electric Company, 
collectively, the ``Joint Stakeholders.'' In the Joint Proposal, the 
signatories recommended DOE adopt a Federal test procedure by 
incorporating by reference industry standards AHAM AC-7-2022 \5\ and 
AHAM AC-1-2020.\6\ In the March 2023 test procedure final rule, DOE 
considered comments received in response to the test procedure NOPR as 
well as the Joint Proposal in adopting the current air cleaners test 
procedures.
---------------------------------------------------------------------------

    \3\ Available at www.regulations.gov/comment/EERE-2024-BT-TP-0011-0002.
    \4\ Representing the following companies who manufacture 
consumer room air cleaners and are members of the Portable Appliance 
Division: 3M Co., ACCO Brands Corporation, Airgle Corporation, 
Alticor, Inc., Beijing Smartmi Electronic Technology Co., Ltd., 
BISSELL Inc., Blueair Inc., BSH Home Appliances Corporation, 
De'Longhi America, Inc., Dyson Limited, Essick Air Products, 
Fellowes Inc., Foxconn Technology Group, Gree Electric Appliances 
Inc., Groupe SEB, Haier Smart Home Co., Ltd., Helen of Troy-Health & 
Home, Lasko Products, Inc., Molekule Inc., Newell Brands Inc., 
Oransi LLC, Phillips Domestic Appliances NA Corporation, SharkNinja 
Operating, LLC, Vornado Air LLC, Winix Inc., and Zojirushi America 
Corporation.
    \5\ AHAM AC-7-2022, ``Energy Test Method for Consumer Room Air 
Cleaners,'' copyright 2022.
    \6\ ANSI/AHAM AC-1-2020, ``Method for Measuring Performance of 
Portable Household Electric Room Air Cleaners,'' ANSI-approved 
December 2020, including AHAM Standard Interpretation on September 
19, 2022.
---------------------------------------------------------------------------

    In announcing this petition for public comment, DOE is seeking 
views on whether it should grant the petition and undertake a 
rulemaking to consider the proposal contained in the petition. DOE 
welcomes comments on any aspect of the petition. By seeking comment on 
whether to grant this petition, DOE takes no position at this time 
regarding the merits of the suggested rulemaking or the assertions in 
Dyson's petition. Accordingly, DOE is not revoking or staying 
enforcement of the provisions referenced in Dyson's petition.

Submission of Comments

    DOE will accept comments, data, and information regarding this 
petition no later than the date provided in the DATES section at the 
beginning of this document. Interested parties may submit comments, 
data, and other information using any of the methods described in the 
ADDRESSES section at the beginning of this document.
    Submitting comments via www.regulations.gov. The 
www.regulations.gov web page will require you to provide your name and 
contact information. Your contact information will be viewable to DOE 
Building Technologies staff only. Your contact information will not be 
publicly viewable except for your first and last names, organization 
name (if any), and submitter representative name (if any). If your 
comment is not processed properly because of technical difficulties, 
DOE will use this information to contact you. If DOE cannot read your 
comment due to technical difficulties and cannot contact you for 
clarification, DOE may not be able to consider your comment.
    However, your contact information will be publicly viewable if you 
include it in the comment or in any documents attached to your comment. 
Any information that you do not want to be publicly viewable should not 
be included in your comment, nor in any document attached to your 
comment. If this instruction is followed, persons viewing comments will 
see only first and last names, organization names, correspondence 
containing comments, and any documents submitted with the comments.
    Do not submit to www.regulations.gov information for which 
disclosure is restricted by statute, such as trade secrets and 
commercial or financial information (hereinafter referred to as 
Confidential Business Information (``CBI'')). Comments submitted 
through www.regulations.gov cannot be claimed as CBI. Comments received 
through the website will waive any CBI claims for the information 
submitted. For information on submitting CBI, see the Confidential 
Business Information section.
    DOE processes submissions made through www.regulations.gov before 
posting. Normally, comments will be posted within a few days of being 
submitted. However, if large volumes of comments are being processed 
simultaneously, your comment may not be viewable for up to several 
weeks. Please keep the comment tracking number that www.regulations.gov 
provides after you have successfully uploaded your comment.
    Submitting comments via email, hand delivery/courier, or postal 
mail. Comments and documents submitted via email, hand delivery/
courier, or postal mail also will be posted to www.regulations.gov. If 
you do not want your personal contact information to be publicly 
viewable, do not include it in your comment or any accompanying 
documents. Instead, provide your contact information on a cover letter. 
Include your first and last names, email address, telephone number, and 
optional mailing address. The cover letter will not be publicly 
viewable as long as it does not include any comments.
    Include contact information each time you submit comments, data, 
documents, and other information to DOE. If you submit via postal mail 
or hand delivery/courier, please provide all items on a CD, if 
feasible, in which case it is not necessary to submit printed copies. 
Faxes will not be accepted.
    Comments, data, and other information submitted to DOE 
electronically should be provided in PDF (preferred), Microsoft Word or 
Excel, WordPerfect, or text (ASCII) file format. Provide documents that 
are not secured, written in English and free of any defects or viruses. 
Documents should not contain special characters or any form of 
encryption and, if possible, they should carry the electronic signature 
of the author.
    Campaign form letters. Please submit campaign form letters by the 
originating organization in batches of between 50 to 500 form letters 
per PDF or as one form letter with a list of supporters' names compiled 
into one or more PDFs. This reduces comment processing and posting 
time.
    Confidential Business Information. According to 10 CFR 1004.11, any 
person submitting information that he or she believes to be 
confidential and exempt by law from public disclosure should submit via 
email two well-

[[Page 17897]]

marked copies: one copy of the document marked confidential including 
all the information believed to be confidential, and one copy of the 
document marked ``non-confidential'' with the information believed to 
be confidential deleted. Submit these documents via email. DOE will 
make its own determination about the confidential status of the 
information and treat it according to its determination.
    It is DOE's policy that all comments may be included in the public 
docket, without change and as received, including any personal 
information provided in the comments (except information deemed to be 
exempt from public disclosure).

Signing Authority

    This document of the Department of Energy was signed on April 21, 
2025, by Louis Hrkman, Principal Deputy Assistant Secretary for Energy 
Efficiency and Renewable Energy, pursuant to delegated authority from 
the Secretary of Energy. That document with the original signature and 
date is maintained by DOE. For administrative purposes only, and in 
compliance with requirements of the Office of the Federal Register, the 
undersigned DOE Federal Register Liaison Officer has been authorized to 
sign and submit the document in electronic format for publication, as 
an official document of the Department of Energy. This administrative 
process in no way alters the legal effect of this document upon 
publication in the Federal Register.

    Signed in Washington, DC, on April 24, 2025.
Treena V. Garrett,
Federal Register Liaison Officer, U.S. Department of Energy.

PETITION FOR AMENDMENT

Before the

UNITED STATES DEPARTMENT OF ENERGY

Office of Energy Efficiency and Renewable Energy

In the Matter of: Energy Conservation Program: Test Procedure for Air 
Cleaners
Docket No. EERE-2021-BT-TP-0036

Petition for Amendment

I. Executive Summary
II. Background
    A. DOE Has Adopted A Test Procedure Poorly Suited To Determining 
Room Size Coverage And IEF Scores for Air Cleaners
    B. In Reliance On DOE, FTC Has Proposed To Adopt The Same Poorly 
Suited Test Procedure
    C. Dyson Has Confirmed That Room Size Coverage Claims And IEF 
Scores Based On The Test Procedure Are Inaccurate And Inconsistent
III. Grounds for Petition
    A. The Room Size Coverage Rule And IEF Rule Require 
Manufacturers To Display Product Claims That Are Inaccurate And 
Inconsistent
    B. The Room Size Coverage Rule And IEF Rule Mislead Consumers
    C. The Room Size Coverage Rule And IEF Rule Stifle Innovation
    D. The Room Size Coverage Rule And IEF Rule Result In Increased 
Energy Consumption
    E. The Room Size Coverage Rule And IEF Rule Should Be, At 
Minimum, Stayed To Provide Time For Notice And Comment On Whether To 
Revoke Or Modify The Rules
IV. Conclusion

    Dyson Inc. (``Dyson'') respectfully petitions the United States 
Department of Energy (``DOE'') pursuant to 5 U.S.C. 553(e) to:
    1. amend part 429 of chapter II, subchapter D, of title 10 of the 
Code of Federal Regulations to remove section 429.68(a)(4), a section 
which requires that ``[a]ny represented value of the effective room 
size, in square feet, of a[n air cleaner] must be calculated as the 
product of 1.55 and the represented smoke CADR value of the [air 
cleaner]'' (the ``Room Size Coverage Rule''); and,
    2. amend part 430 of chapter II, subchapter D, of title 10 of the 
Code of Federal Regulations to remove section 430.23(hh)(4), a section 
which requires that ``[t]he annual energy consumption, expressed in 
kilowatt-hours per year, and the integrated energy factor, expressed in 
CADR per watts (CADR/W), for conventional room air cleaners, shall be 
measured in accordance with section 7 of appendix FF of this subpart'' 
(the ``IEF Rule'').

I. Executive Summary

    DOE implemented the Room Size Coverage Rule and the IEF Rule on 
March 6, 2023 (effective December 31, 2023) to establish standard 
procedures by which manufacturers may measure and represent to 
consumers the effective room size coverage and integrated energy factor 
(``IEF'') scores of their air cleaner products. In enacting these 
rules, DOE stated that it ``considers room size [and IEF, which is a 
`function of the room size that the unit is expected to operate in'] to 
be an important metric that must be represented accurately and 
consistently to provide meaningful information to consumers.'' \7\ 
Dyson agrees. It is important for consumers to have accurate 
information about the efficacy and efficiency with which different air 
cleaners clean various sized rooms. Unfortunately, the Room Size 
Coverage Rule and the IEF Rule do exactly the opposite.
---------------------------------------------------------------------------

    \7\ Energy Conservation Program: Test Procedures for Air 
Cleaners, 88 FR 14014 at 8 (Mar. 6, 2023), at 21.
---------------------------------------------------------------------------

    Dyson, therefore, petitions DOE to revoke the Room Size Coverage 
Rule and the IEF Rule because they: (1) obligate manufacturers to make 
frequently inaccurate and misleading claims about the efficacy and 
efficiency with which their products operate, (2) stifle innovation by 
manufacturers to develop products that operate better where it counts--
in consumers' homes--rather than in a highly stylized test chamber, and 
(3) undermine energy efficient consumer purchasing decisions in 
violation of DOE's broader mandate to properly ``regulate the energy 
efficiency of [ ] consumer products . . . .'' \8\
---------------------------------------------------------------------------

    \8\ 42 U.S.C. 6291-6317.
---------------------------------------------------------------------------

    More particularly, the Room Size Coverage Rule and the IEF Rule 
should be revoked because they obligate manufacturers to express air 
cleaner room size coverage and IEF scores using clean air delivery 
rates (``CADR'') measured in reliance on the test procedure AHAM-AC-1-
2020 (the ``AHAM CADR Test''), incorporated by reference into Appendix 
FF to Subpart B of Part 430, Title 10. As explained herein, the AHAM 
CADR Test suffers from severe flaws that result in CADRs that do not 
have real-world validity and, when used to calculate room size coverage 
and IEF scores, result in misleading information reaching consumers 
about the absolute and relative capabilities of different air cleaners 
to effectively and efficiently clean various sized rooms.
    These concerns are not new to DOE. Manufacturers, including Dyson, 
submitted comments during the notice and comment period in December 
2022 urging DOE not to adopt mandates that would result in inaccurate 
and inconsistent measures of room size coverage and energy efficiency. 
DOE rejected these comments on the basis that, in summary, `something 
is better than nothing.' Dyson disagrees when the `something' results 
in misleading consumers, stifling innovation and wasteful energy 
consumption.
    Dyson has subsequently developed test data and retained external 
experts to review Dyson's test data and perform a literature review. 
The expert report of Dr. Timothy Morse, Ph.D., and Dr. Khaled Hashad, 
Ph.D., of Exponent, is annexed hereto as Exhibit A (the ``Exponent 
Report''). Like Dyson,

[[Page 17898]]

experts Morse and Hashad conclude that the AHAM CADR Test does not 
produce reliable CADRs that can be used to measure the efficacy and 
efficiency with which air cleaners can clean various sized rooms.
    Based upon this new and accumulating body of evidence, Dyson urges 
DOE to revoke the Room Size Coverage Rule and IEF Rule or, to the 
extent that DOE after full consideration of this Petition still wishes 
to impose a one-size-fits-all test for room size coverage claims and 
IEF scores, stay enforcement of the Room Size Coverage Rule and IEF 
Rule and open a period of notice and comment so the public can submit 
their views on how, if at all, DOE can mandate a test procedure with 
greater real-world validity.
    The importance of this petition is underscored by the recent 
proposed rulemaking by the United States Federal Trade Commission 
(``FTC''), which has proposed to add room size coverage claims to its 
required EnergyGuide labels on air cleaners, and to mandate that room 
size coverage numbers must be calculated using the standard adopted by 
DOE--i.e., the Room Size Coverage Rule.\9\ Dyson has opposed the FTC's 
rulemaking in written comments \10\ and will present its critiques 
during a hearing scheduled for September 19, 2024. FTC has not yet 
issued a final rule and DOE can take this opportunity to revoke the 
Room Size Coverage Rule and IEF Rule and avoid agencies like FTC 
``doubling down'' on DOE's flawed approach.
---------------------------------------------------------------------------

    \9\ Energy Labeling Rule, 89 FR 7566, 7568 (Feb. 2, 2024).
    \10\ Comment from Dyson, Inc., REGULATIONS.GOV (Mar. 19, 2024), 
https://www.regulations.gov/comment/FTC-2024-0008-0010; Comment from 
Dyson, Inc., REGULATIONS.GOV (April 19, 2024), https://www.regulations.gov/comment/FTC-2024-0008-0022.
---------------------------------------------------------------------------

II. Background

A. DOE Has Adopted a Test Procedure Poorly Suited To Determining Room 
Size Coverage and IEF Scores for Air Cleaners

    On March 6, 2023, DOE published a final rule entitled Energy 
Conservation Program: Test Procedure for Air Cleaners.\11\ The final 
rule, incorporating the Room Size Coverage Rule and IEF Rule, mandated 
that all representations to consumers concerning the room size coverage 
capabilities of air cleaners and all IEF scores must be calculated 
using CADRs measured in reliance on the AHAM CADR Test.\12\ DOE 
implemented the final rule over the objections of Dyson and other air 
cleaner manufacturers on the ground that it is important to require a 
standard method for substantiation of room size coverage claims and IEF 
scores. The final rule went into effect on December 31, 2023.
---------------------------------------------------------------------------

    \11\ Energy Conservation Program: Test Procedures for Air 
Cleaners, 88 FR 14014 (Mar. 6, 2023).
    \12\ Id. at 8.
---------------------------------------------------------------------------

    CADR is not a measure of room size coverage or energy consumption. 
Likewise, the AHAM CADR Test is not designed to measure the size of the 
room that an air cleaner is capable of cleaning or its energy 
consumption. CADR is a measure of the clean air volume that an air 
cleaner can provide in a fixed amount of time and space. It is the air 
cleaner equivalent of a vehicle's 0-60 mph acceleration test, as it 
measures an air cleaner's purification speed on the maximum fan mode 
within a 28 m\3\ chamber. In practical terms, it measures how quickly 
an air cleaner can remove a pollutant from a room (e.g., how quickly 
can it remove the smell of burnt toast from a kitchen). Consumers are 
not using air cleaners primarily, let alone exclusively, for such a 
narrow purpose.
    The AHAM CADR Test is a nearly 40-year-old test procedure (albeit 
updated from time to time) developed by the Association of Home 
Appliance Manufacturers (``AHAM''). The test is performed in a small 
chamber (28 m\3\) equipped with a single sensor to monitor the particle 
count in the air and two fans to circulate the air: a ceiling fan and a 
powerful wall-mounted recirculation fan. Before the test begins, the 
test subject air cleaner is placed in the center of the chamber, 
manually set to maximum speed and both the ceiling and wall mounted 
recirculation fans are switched on. The air cleaner remains operating 
at full speed throughout the duration of the test; there is no 
provision made for automatic sensor-response or standby modes. A 
controlled amount of pollutant is then pumped into the room, allowing 
the fans in the chamber to mix and homogenize the pollutant 
concentration before pollutant levels in this ``well-mixed'' room are 
measured by the single sensor. At the start of the test, the ceiling 
fan is turned off, but the recirculation fan remains running. The test 
lasts for 20 minutes. Following the test, a `CADR Score' is calculated 
by measuring how much faster the air cleaner removed particles from the 
air compared to how fast the particles would naturally have `decayed' 
or dropped and settled on surfaces but for the air cleaner, which is 
then multiplied by the volume of the test chamber. The below image at 
Figure 1 illustrates the setup of a CADR test chamber.

[[Page 17899]]

[GRAPHIC] [TIFF OMITTED] TP30AP25.045

Figure 1.13
---------------------------------------------------------------------------

    \13\ ANSI/AHAM AC-1-2020, p.1 (pdf p. 26).
---------------------------------------------------------------------------

    There are a number of problems with the design of the AHAM CADR 
Test which render it inapt to measure CADRs used for determining room 
size coverage or energy consumption. For example, the AHAM CADR Test:
     Measures short-term performance only. The AHAM CADR Test 
measures how quickly an air cleaner can clean the air in a standardized 
room (e.g., how quickly it can remove the smell of burnt toast from a 
kitchen) when the contaminated air is pressurized by the recirculation 
fan and `fed' to the air cleaner. The test does not measure whether an 
air cleaner can clean a room of a given size and keep it clean over a 
sustained period under real-world conditions, which is the typical 
application of an air cleaner.
     Uses a high-powered fan to homogenize the air and move it 
toward the air cleaner. The AHAM CADR Test uses an active system (a 
high-powered recirculation fan), which homogenizes and pushes the air 
toward the air cleaner. The active system obscures important 
distinctions between air cleaners that do and do not have lateral 
whole-room air distribution technology (their own powerful, built-in 
fans), giving air cleaners without consumer-benefiting lateral air 
distribution artificial boosts in performance relative to those that 
do.
     Places the air cleaner in the center of the test chamber. 
The AHAM CADR Test requires that the tester place the air cleaner in 
the center of the test chamber with only one sensor in the chamber 
testing how well the air cleaner has cleaned the chamber, rather than 
placing the air cleaner against a wall or in a corner--where consumers 
typically place air cleaners--and using multiple sensors to evaluate 
how well the air cleaner is cleaning the whole test chamber. These 
aspects of the test procedure obscure material differences in 
technology like lateral whole-room air distribution, which help to 
ensure wider coverage of a room by an air cleaner even when placed (as 
is typical) against a wall or in a corner.
     Uses a small test chamber. The AHAM CADR Test chamber is 
considerably smaller than most rooms in consumers' homes. This is 
significant since the AHAM CADR Test is highly sensitive to different 
size chambers, resulting in arbitrary room size coverage claims when 
results are extrapolated to larger size rooms.
     Operates air cleaners in maximum power mode. The AHAM CADR 
Test requires that air cleaners remain at maximum fan speed during the 
entirety of the test, which ignores air cleaner sensor technologies in 
many but not all modern air cleaners that match the speed of the 
internal fan to the level of pollutants in the air. This test 
requirement undermines energy efficient purchasing decisions by 
consumers, who in the real world will run their air cleaners on 
``normal'' or ``automatic'' modes both as a matter of energy efficiency 
and comfort (maximum power modes are loud), which modes are not 
reflected in room size coverage claims made based on CADR.
    On October 18, 2022, DOE published a Notice of Proposed Rulemaking 
(``NOPR'') \14\ and opened a comment period which ended on December 19, 
2022. In the NOPR, DOE requested, among other things, comments on a 
proposal to use CADR to calculate the effective room size that can be 
serviced by an air cleaner and ``whether it is appropriate to use smoke 
CADR as the metric to calculate effective room size or if it should be 
based on PM2.5 CADR instead [which includes smoke and other 
pollutants].'' \15\ DOE presented the choice as binary (smoke vs. a mix 
of

[[Page 17900]]

smoke and other pollutants) and did not ask whether CADR itself is 
suitable for calculating effective room size or IEF score or whether 
the AHAM CADR Test was an appropriate procedure to calculate CADR for 
these purposes.
---------------------------------------------------------------------------

    \14\ 2022-10-18 Energy Conservation Program: Test Procedure for 
Air Cleaners; Notice of proposed rulemaking and request for comment, 
REGULATIONS.GOV (Oct. 18, 2022), at 19, https://www.regulations.gov/document/EERE-2021-BT-TP-0036-0018.
    \15\ 2022-11-09 Presentation: Air Cleaners Test Procedure: 
Notice of Proposed Rulemaking Public Meeting--REGULATIONS.GOV (Nov. 
9, 2022), at 49, https://www.regulations.gov/document/EERE-2021-BT-TP-0036-0024.
---------------------------------------------------------------------------

    Dyson opposed DOE's adoption of CADR, stating in a comment that the 
range of air cleaner technologies and home environments precludes a 
one-size-fits-all room size calculation--particularly in a mandatory 
regulatory context.\16\ Dyson cautioned DOE not to base room size 
coverage determinations on CADR, as the metric and performance output 
from the AHAM CADR Test methodology does not accurately reflect real-
life performance.\17\ In particular, Dyson urged that CADR is 
unsuitable for calculating room size coverage because:
---------------------------------------------------------------------------

    \16\ 2022-12-16 Dyson Comment response to the published Notice 
of proposed rulemaking and request for comment, REGULATIONS.GOV 
(Dec. 16, 2022), at 1-2, https://www.regulations.gov/comment/EERE-2021-BT-TP0036-0027.
    \17\ At various points during the DOE's rulemaking, other 
commenters expressed concerns about the validity or usefulness of 
CADR as well. See, e.g., 2024-02-24 Synexis Comment response to the 
published Reopening of Comment Period; Request for information, 
REGULATIONS.GOV (Apr. 11, 2022), at 4, https://www.regulations.gov/comment/EERE-2021-BT-TP-0036-0009 (noting that ``CADR test chambers 
are not representative of actual room sizes, and therefore CADR 
ratings do not reflect actual usage under real-world conditions.'').
---------------------------------------------------------------------------

    1. Manufacturers already offer nuanced estimates of room size 
coverage customized for different environments and technologies, and 
collapsing the measurement of room size coverage claims to a single 
methodology withholds consumer relevant information tailored to 
consumers' differing needs and manufacturers' differing offerings.
    2. The AHAM CADR Test uses a recirculation fan that is not present 
in real-world spaces and gives air cleaners with poor or no lateral 
whole-room air circulation an artificial boost in room size coverage.
    3. The AHAM CADR Test runs all models on maximum and does not 
account for automatic sensor-response modes, which are common in 
today's marketplace and impact real-world room size coverage 
capabilities.
    4. Room size coverage claims calculated using CADR do not scale 
properly and are inaccurate.
    Similarly, Synexis LLC submitted a comment asserting that ``CADR 
ratings do not reflect actual usage under real-world conditions.'' \18\ 
Synexis' criticism focused on the size of the test chambers, which 
``are not representative of actual room sizes.'' \19\ Synexis instead 
advocated for ``[t]esting in large chambers,'' as such chambers are 
``more appropriate . . . [and] more representative of real world 
conditions.'' \20\ Synexis expressed concern that ``using CADR[] alone 
. . . might be misleading with regard to overall energy consumption 
required to achieve maximum effectiveness.'' \21\ Likewise, Molekule, 
Inc. criticized CADR for failing to account for the benefits of 
different technologies offered with different air cleaners.\22\ 
Molekule expressed concern that using a standard test method would be 
bad for consumers and for achieving energy efficiency, asserting that 
``energy standards based solely on traditional [AHAM CADR Test]-based 
testing methods that only focus on particulate capture are likely to 
hinder the development and distribution of innovative devices . . . .'' 
\23\
---------------------------------------------------------------------------

    \18\ 2024-02-24 Synexis Comment response to the published 
Reopening of Comment Period; Request for information, 
REGULATIONS.GOV (Apr. 11, 2022) at 4, https://www.regulations.gov/comment/EERE-2021-BT-TP0036-0009.
    \19\ Id.
    \20\ Id. at 5
    \21\ Synexis discussed other test methods which may be 
alternatives to CADR, including AHAM-AC-5-2022 (2022), the Research 
Triangle Institute test method, and the National Research Council 
Canada rest method. (See Id., at 3-4).
    \22\ 2022-04-09 Molekule Comment response to the published 
Reopening of Comment Period; Request for information, 
REGULATIONS.GOV (Apr. 11, 2022), https://www.regulations.gov/comment/EERE-2021-BT-TP-00360012.
    \23\ 2024-02-24 Synexis Comment response to the published 
Reopening of Comment Period; Request for information, 
REGULATIONS.GOV (Apr. 11, 2022) at 2, https://www.regulations.gov/comment/EERE-2021-BT-TP0036-0009.
---------------------------------------------------------------------------

    DOE acknowledged in its final rulemaking that the AHAM CADR Test 
does not reflect real-world spaces (in particular, the use of a 
powerful recirculation fan) and does not account for commonplace modern 
air cleaner technologies (for example, automatic sensor-response mode 
and built-in lateral whole-room air circulation). Further, DOE admitted 
that there is no current test procedure for air cleaners in automatic 
mode that measures energy efficiency.\24\ Nevertheless, DOE adopted the 
final rule as DOE initially proposed.
---------------------------------------------------------------------------

    \24\ Energy Conservation Program: Test Procedures for Air 
Cleaners, 88 FR 14014 at 8 (Mar. 6, 2023).
---------------------------------------------------------------------------

B. In Reliance on DOE, FTC Has Proposed To Adopt the Same Poorly Suited 
Test Procedure

    On February 2, 2024, FTC published a Notice of Proposed Rulemaking 
(89 FR 7566),\25\ proposing to adopt the Room Size Coverage Rule for 
room size coverage claims on EnergyGuide Labels,\26\ which 
manufacturers are required to include on air cleaner product packaging. 
The proposed rule has the potential to magnify the harm to consumers 
and innovators already being caused by DOE's Room Size Coverage Rule 
and--to the extent DOE determines that it should revoke the Room Size 
Coverage Rule--to create administrative headaches across multiple 
agencies and impose otherwise unnecessary economic burdens on 
manufacturers.
---------------------------------------------------------------------------

    \25\ Energy Labeling Rule, 89 FR 7566, 7568 (Feb. 2, 2024). 
https://www.regulations.gov/document/FTC2024-0008-0001.
    \26\ See Energy Labelling Rule, 16 CFR part 305.
---------------------------------------------------------------------------

    Dyson submitted two comments to FTC on March 18, 2024,\27\ and 
April 19, 2024.\28\ In its comments, Dyson emphasized its concerns that 
adoption of the Room Size Coverage Rule would lead to consumer 
confusion and stifle innovation in the market for air cleaners. Dyson 
urged FTC not to ``double down'' on a flawed approach to substantiation 
of room size coverage claims until DOE has had an opportunity to 
consider this petition. Fortunately, FTC has not acted on its proposal 
and has granted Dyson's request for a hearing, scheduled for September 
19, 2024. The potential for agency action resulting in additional 
consumer, manufacturer and regulatory harm stemming from the Room Size 
Coverage Rule and IEF Rule nevertheless underscores the need for DOE to 
take a second look at the Rules now.
---------------------------------------------------------------------------

    \27\ Comment from Dyson, Inc., REGULATIONS.GOV (Mar. 18, 2024), 
https://www.regulations.gov/comment/FTC-20240008-0010 (containing 
initial comments and requesting a hearing).
    \28\ Comment from Dyson, Inc., REGULATIONS.GOV (April 19, 2024), 
https://www.regulations.gov/comment/FTC2024-0008-0022 (providing 
further comments and re-iterating request for a hearing).
---------------------------------------------------------------------------

C. Dyson Has Confirmed That Room Size Coverage Claims and IEF Scores 
Based on CADR are Inaccurate

    After DOE's issuance of the Room Size Coverage Rule, Dyson has 
performed additional testing on a range of air cleaner models sold by 
manufacturers in the US (1) using the AHAM CADR Test, (2) using the 
AHAM CADR Test with corrections for certain of its flaws, and (3) under 
simulated real-world conditions. The data from testing performed by 
Dyson demonstrate that the Room Size Coverage Rule and IEF Rule 
obligate manufacturers who make room size coverage and IEF claims to 
publish inaccurate and inconsistent representations about their 
products that inevitably result in misleading consumers, stifling 
innovation and increasing energy inefficiency. Dyson retained Dr. Tim 
Morse, Ph.D., and Dr. Khaled Hashad, Ph.D., of Exponent to perform an 
evaluation of Dyson's data and the relevant literature. Drs. Morse

[[Page 17901]]

and Hashad came to the same conclusions, as discussed herein and in the 
attached Exponent Report.

III. Grounds for Petition

    For the reasons highlighted below and in the Exponent Report, Dyson 
petitions DOE to amend 29 CFR 429 and 430 to revoke the Room Size 
Coverage Rule and IEF Rule. DOE intended to provide consumers with 
benchmarks to select the most effective and efficient air cleaner for 
their rooms. However, room size coverage claims and IEF scores 
calculated with CADR measured using the AHAM CADR Test are inaccurate 
and inconsistent, and result in consumer confusion, stifled innovation 
and increased energy consumption.
    If, however, DOE believes that these claims must be standardized 
via regulation, Dyson respectfully submits that the Room Size Coverage 
Rule and IEF Rule should be stayed pending a new notice and comment 
period concerning proposed substitutions for, or modifications to, the 
AHAM CADR Test that would allow CADRs used in determining room size 
coverage claims and IEF scores to have greater real world validity, and 
thus, give consumers more relevant and less deceptive information about 
the energy efficacy and efficiency of air cleaners.

A. The Room Size Coverage Rule and IEF Rule Require Manufacturers To 
Display Product Claims That are Inaccurate and Inconsistent, Thereby 
Misleading Consumers About the Right Air Cleaners for Their Homes

    Dyson tested seven name-brand air cleaner units with varying 
features using the chamber prescribed by the AHAM CADR Test and using 
chambers better reflecting real-world conditions (e.g., larger 
chambers, air cleaners in the corners of the chambers, and no high-
powered recirculation fans in the chambers). As shown in the data and 
summarized in Figure 2(a), below and to the left, for most air cleaners 
(5 out of 7 that were tested), the AHAM CADR Test artificially inflates 
the CADR scores by as much as 45%. Moreover, there is no consistency 
across tested units in terms of inflation (or deflation for 1 out of 
7). Thus, AHAM CADR Test-based CADR scores are not only inaccurate, but 
also inconsistent and cannot serve as a basis to discern relative 
performance. This is problematic for consumers as the energy efficiency 
and efficacy of an air cleaner may be significantly lower than the 
efficiency and efficacy purportedly measured using the AHAM CADR Test 
and advertised on the product pursuant to the Room Size Coverage Rule 
and IEF Rule.
[GRAPHIC] [TIFF OMITTED] TP30AP25.046

Figures 2(a) and (b).29
---------------------------------------------------------------------------

    \29\ See Exponent Report at 26-27. CADR obtained for various air 
cleaner products tested using the AHAM standard and tested under 
typical indoor conditions (larger chamber (81 m\3\), air cleaner at 
the corner, and no external mixing). (a) For most air cleaners the 
AHAM standard test resulted in an increase in CADR that can reach up 
to 45%, (b) products 3 and 7 had similar CADR in the AHAM test but 
product 7 had a 15% decrease in CADR compared to product 6 when 
tested in typical indoor conditions.
---------------------------------------------------------------------------

    The inaccuracy and lack of consistency among CADR scores is because 
the AHAM CADR Test is an inappropriate test method for determining room 
size coverage (and, therefore, IEF scores, which DOE has said are 
``inherently a function of the room size that the unit is expected to 
operate in'' \30\). The AHAM CADR Test was designed to enable 
scientific, repeatable testing of an air cleaner's speed of cleaning in 
isolated laboratory conditions. It was not designed to provide an 
accurate representation of how these products perform in larger rooms 
under real-world conditions--i.e., in consumers' homes. This is evident 
from the prescribed test environment, which is not relevant to, or 
reflective of, real-world environments in which consumers will use the 
tested air cleaners, as follows:
---------------------------------------------------------------------------

    \30\ Energy Conservation Program: Test Procedures for Air 
Cleaners, 88 FR 14014 at 8 (Mar. 6, 2023), at 21.
---------------------------------------------------------------------------

1. The Test Chamber Contains a High-Powered Fan \31\
---------------------------------------------------------------------------

    \31\ See Exponent Report at Section 4.1 at 19-20.
---------------------------------------------------------------------------

    The AHAM CADR Test chamber contains a powerful, wall-mounted 
recirculation fan which operates continuously during testing to achieve 
artificial mixing. The fan circulates and mixes particles introduced 
into the test chamber, evenly spreading the particles to create a 
homogeneous environment so that readings taken by the single sensor 
approximate particle concentrations across the chamber. This is highly 
stylized and unrealistic. Many consumer homes do not have any fans at 
all \32\ and are unlikely to have an `even spread' of pollutants. 
Moreover, fans used in real-world spaces are not comparable to the 
recirculation fan used in a CADR test--as the latter is extremely 
powerful, requires a substantial amount of energy to operate and 
essentially `feeds' the polluted air to the air cleaner, which may have 
limited ability to circulate and push the air itself. Figure 3, below, 
illustrates the significant power of the recirculation fan recommended 
in the AHAM CADR Test standard.
---------------------------------------------------------------------------

    \32\ A 2020 Residential Energy Consumption Survey by the U.S. 
Energy Information Administration found that most U.S. apartments 
did not have any ceiling fan, and of 123.53m U.S. homes surveyed (of 
all sizes) 34.08m had no ceiling fans. Source: https://www.eia.gov/consumption/residential/data/2020/hc/pdf/HC%207.1.pdf.
---------------------------------------------------------------------------

BILLING CODE 6450-01-P

[[Page 17902]]

[GRAPHIC] [TIFF OMITTED] TP30AP25.047

Figure 3.
---------------------------------------------------------------------------

    \33\ Assumed 8 hours daily use on maximum power at $0.15 per 
kWh.
---------------------------------------------------------------------------

    Figure 4 below displays the CADR for various air cleaners tested 
with and without artificial mixing and in two different chamber sizes 
(28 m\3\ and 81 m\3\). The test data indicate that for air cleaners 
with builtin lateral whole-room air circulation technology (that 
ensures whole-room air circulation in the real world in consumers' 
homes) the artificial mixing has no impact on the CADR score (1 and 3). 
However, for air cleaners that do not have technology sufficient to 
circulate the air in consumers' homes (2, 5-7),\34\ the artificial 
mixing can erroneously increase the CADR by up to 32%, rendering room 
size coverage claims and IEF scores calculated using CADR absolutely 
and relatively inaccurate.\35\
---------------------------------------------------------------------------

    \34\ Air cleaner 4 performed near-equally well on both tests, 
despite not being equipped with lateral whole-room air circulation 
technology. Why that model performed differently than similarly 
situated models 2, 5, 6 and 7 is beyond the scope of this petition, 
but the disparity further illustrates the unreliability of CADR for 
predicting realworld performance.
    \35\ See Exponent Report at 8. Moreover, an air cleaner can only 
clean air that passes through its filter. Without the presence of a 
powerful recirculation fan to circulate air (and the pollutants), 
natural air movement may never be powerful enough to move pollutants 
from the far side of a room to an air cleaner unless the air cleaner 
has builtin air circulation and mixing technology.
[GRAPHIC] [TIFF OMITTED] TP30AP25.048

BILLING CODE 6450-01-C

[[Page 17903]]

Figure 4.36
---------------------------------------------------------------------------

    \36\ See Exponent Report at 20. The CADR for various air cleaner 
products tested in two different test chamber sizes, 28 m\3\ and 81 
m\3\, with and without mixing. For some products the use of a 
recirculation fan (mixing) resulted in minimal changes in CADR, 
while for other products it resulted in an increase of CADR by up to 
32%.
---------------------------------------------------------------------------

    This flaw results in a perverse outcome where the more effective 
and technologically advanced air cleaners score worse relative to other 
air cleaners. The high-powered recirculation fan is essentially giving 
all air cleaners ``credit'' for having lateral whole-room air 
circulation technology that enables more effective cleaning of the 
room. The fan is doing the work for the air cleaners that do not do it 
themselves.
2. The Air Cleaner is Placed in the Center of the Test Chamber \37\
---------------------------------------------------------------------------

    \37\ See Exponent Report, Section 4.3 at 23-25.
---------------------------------------------------------------------------

    The AHAM CADR Test places the air cleaner in the center of the 
testing chamber. However, consumers are much more likely to place an 
air cleaner in the corner of a room or against a wall than in the 
center of a room. Placement against a wall or in a corner is not only 
logical from a practical and common sense perspective (as this is where 
outlets are usually located and consumers will generally not want an 
air cleaner `getting in the way' by placing it in the center of a 
room), but Dyson has undertaken owner surveys which found that only a 
small minority (17%) of users placed an air cleaner in the center of 
their room, whereas 43% placed it in the corner and 40% placed it up 
against a wall, as reflected in Figure 5, below.
[GRAPHIC] [TIFF OMITTED] TP30AP25.049

Figure 5.38
---------------------------------------------------------------------------

    \38\ Survey data from 584 Dyson air cleaner owners across 
Canada, France, and Australia relating to air cleaner placement in 
consumer homes. Conducted in 2016.
---------------------------------------------------------------------------

    Location matters. Indeed, a study that investigated the CADR of an 
air cleaner located at four different locations in an office space 
showed that the CADR can vary by up to 27% (compared to the average) 
depending on its location in the room.\39\ Thus, testing with an air 
cleaner in the center of the room is not reflective of likely usage 
conditions and could materially skew results.
---------------------------------------------------------------------------

    \39\ K[uuml]pper, M., Asbach, C., Schneiderwind, U., Finger, H., 
Spiegelhoff, D., & Schumacher, S. (2019). Testing of an indoor air 
cleaner for particulate pollutants under realistic conditions in an 
office room. Aerosol and Air Quality Research, 19(8), 1655-1665.
---------------------------------------------------------------------------

    Dyson tested air cleaners in both 81 m\3\ and 169 m\3\ test 
chambers with no mixing and different cleaner locations (center or 
corner). As shown in Figure 6, below, placing an air cleaner in the 
corner of the chamber instead of the center can result in a 
significantly lower CADR. In the most extreme case, placing the air 
cleaner in the center, instead of the corner, resulted in a 34% 
increase in CADR.

[[Page 17904]]

[GRAPHIC] [TIFF OMITTED] TP30AP25.050

Figure 6.40
---------------------------------------------------------------------------

    \40\ See Exponent Report at 25. The CADR for various air cleaner 
products tested by Dyson in two different test chamber sizes, 81 and 
169 m\3\, without mixing, with the air cleaner placed in the corner 
and center of the test chamber. For some products the placement of 
the air cleaner resulted in minimal changes in CADR, while for other 
products it resulted in an increase of CADR by up to 34% when the 
air cleaner was moved from the corner to center of the room.
---------------------------------------------------------------------------

    Thus, placement of the air cleaner in the center of the test 
chamber is both misleading (because it artificially increases the CADR) 
and unfair (because it benefits some air cleaners that do not have 
lateral whole-room air circulation more than air cleaners that do).
3. The Test Chamber is Smaller Than Consumers' Average Rooms and Relies 
on a Single Sensor \41\
---------------------------------------------------------------------------

    \41\ See Exponent Report, Section 4.2 at 20-23.
---------------------------------------------------------------------------

    Consumer survey data obtained by Dyson found that, in the U.S., 52% 
of homes had a family room larger than 360 square feet (19 m\2\).\42\ 
In addition, it is generally accepted that an `average' family room in 
the U.S. is approximately 400 square feet (20 m\2\).\43\ The AHAM CADR 
Test chamber is considerably smaller; it is the equivalent of only 125 
square feet (12 m\2\). Furthermore, houses (and rooms in houses) have 
become larger over the last 30-40 years, compared to when the AHAM CADR 
Test was first developed in the 1980s. According to data from the 
Census Bureau, family homes built in 1990 were 2,080 ft\2\ (193 m\2\) 
on average. By 2015, family homes had increased to an average of 2,687 
ft\2\ (250 m\2\) and for 2022 the average family home was 2,383 ft\2\ 
(221 m\2\).\44\
---------------------------------------------------------------------------

    \42\ Survey of Dyson product owners based in the US conducted in 
2016, with 361 respondents.
    \43\ Jessica Walrack, How Much Square Footage Do You Need? 
Updated on December 14, 2021, https://www.thebalancemoney.com/how-much-square-footage-do-you-need-5201264.
    \44\ Highlights of 2023 Characteristics of New Housing, 2023 
https://www.census.gov/construction/chars/highlights.html.
---------------------------------------------------------------------------

    It is easier for an air cleaner to clean and remove pollutants 
contained in a smaller space than a larger one. In a CADR chamber-sized 
space (125 square feet), even with pollutants at the furthest distance 
from an air cleaner, this will be a relatively short distance and 
relatively easy to clean.
    The larger a room, the further away pollution events (e.g., fumes 
from cooking or pollen or pollution from outside) may be. Without the 
aid of a powerful recirculation fan (as discussed above), an air 
cleaner will need to bring these pollutants to it via its own means, in 
addition to natural circulation, to filter them.
    Figure 7, below, demonstrates that CADR for different air cleaners 
in test chambers 28 m\3\ and 81 m\3\ with ``mixing'' (aka a powerful 
recirculation fan) can vary by up to 16%. These differences are likely 
to lead to misidentification of the air cleaner with the best CADR 
performance.\45\
---------------------------------------------------------------------------

    \45\ See Exponent Report at 22.

---------------------------------------------------------------------------

[[Page 17905]]

[GRAPHIC] [TIFF OMITTED] TP30AP25.051

Figure 7.46
---------------------------------------------------------------------------

    \46\ See id. CADR for various air cleaners tested in a 28 and 81 
m3 chamber. Testing in different test chamber sizes can result in a 
16% difference in CADR.
---------------------------------------------------------------------------

    For example, for the 28 m\3\ size test chamber (the size prescribed 
by the AHAM CADR Test), air cleaner #6 performs better, i.e., has a 
higher CADR than air cleaner #3. However, when the test chamber size is 
closer to real room sizes (81 m\3\), air cleaner #3 performs better, 
i.e., has the higher CADR. Thus, with respect to CADR in a real-world 
room, air cleaner #3 is the better appliance but the AHAM standard 
would identify air cleaner #6 as the higher-performing appliance--and, 
pursuant to the Room Size Coverage Rule and IEF Rule--air cleaner #6 
also would be identified to consumers as covering a larger-sized room 
than air cleaner #3 and with a potentially higher IEF score.
    As discussed above, to achieve more effective large room cleaning, 
certain air cleaners have builtin lateral whole-room air circulation 
and mixing technology to ensure that pollutants on one side of a large 
room are moved around the room and towards the air cleaner. An air 
cleaner without such technology will not be able to do this 
effectively. Built-in air circulation and mixing technology are not 
standard in air cleaners, and products with such technology widely 
range in terms of their strength and capacity. Testing in a small 28 
m\3\ chamber does not enable such capability or technology to be 
properly tested, as even an air cleaner without built-in air 
circulation and mixing technology will be able to more easily clean the 
chamber at that size. This makes the small AHAM CADR Test chamber 
unsuitable for measuring an air cleaner's ability to clean larger 
spaces. In some scenarios, an air cleaner simply will be unable to 
clean a room greater than a certain size (regardless of CADR score) 
because it has insufficient lateral air circulation to push faroff 
pollutants into its filter.
    The problems with using a small test chamber are compounded by 
using only one sensor to test purification and having the cleaner in 
the center of the room. Again, these components of the AHAM CADR Test 
fail to give the resulting CADR relevance to consumers in real world 
spaces. In real world spaces, most consumers will place cleaners in the 
corner of (larger) rooms, and will want to know not how clean the room 
is right next to the air cleaner (as tested by the single sensor in the 
AHAM CADR Test chamber), but rather, how clean the room is in various 
locations, including most importantly where people are located in the 
room. Studies have shown that the CADR can change up to 35.7% based on 
the test chamber volume.\47\ Notably, other international standards 
\48\ specify a test chamber size based on the air cleaners' CADR, which 
better accounts for the impact of chamber volume on CADR measurement.
---------------------------------------------------------------------------

    \47\ Fan, Y., Liu, J., Zhao, L., Wang, C., Moon, D., & Song, S. 
(2024). Study on the test accuracy of the high-air-volume cleaner 
under different test chamber volumes. Journal of Cleaner Production, 
448, 141684.
    \48\ E.g., (GB/T18801-2022) and (SPS-KACA002-132:2021).
---------------------------------------------------------------------------

4. The Test Fails To Account for Automatic Sensor-Response Technology 
\49\
---------------------------------------------------------------------------

    \49\ Exponent Report, Section 6 at 34-35.
---------------------------------------------------------------------------

    The AHAM CADR Test requires the tested air cleaner to operate at 
maximum fan speed throughout the duration of the test and, therefore, 
does not account for increasingly prevalent automatic sensor-response 
mode technology, which adjusts fan speed based on the level of 
pollution in the room in order to conserve energy and increase consumer 
comfort.
    In the same way that a thermostat regulates a home's heating system 
depending on the temperature, an air cleaner with automatic sensor-
response technology monitors and senses the air quality in a room and 
intelligently adjusts fan speed to respond to `pollution events' (for 
example: fumes from cooking or using cleaning products). This 
technology is now widely adopted by modern air cleaners and is a driver 
of consumer purchasing decisions. Of the top 50 selling air cleaners in 
the U.S. by revenue share, over 56% of this revenue is from products 
with some form of automatic response technology.\50\ The consumer 
benefits from automatic sensor-response technology because the air 
cleaner uses no more energy than necessary to clean the room. There 
also is an acoustic benefit offered by the lower fan speeds of 
``smart'' air cleaners using this technology, which reduces noise 
pollution.
---------------------------------------------------------------------------

    \50\ Based on air cleaner sales data in the United Sates for the 
12 months between January 2023 and December 2023.

---------------------------------------------------------------------------

[[Page 17906]]

    If an air cleaner is always run at the maximum fan speed it will 
inevitably `overclean' the space, as it will keep running even once a 
pollution event has been cleaned, thereby wasting energy. It is also 
not reflective of how many air cleaner products available on the market 
today operate, and thus not reflective of what a large proportion of 
consumers owning air cleaners will experience.
    The Room Size Coverage Rule and IEF Rule are intended to measure 
and encourage more energy efficient choices by consumers, ensuring that 
consumers have an accurate representation of how large a space an air 
cleaner can effectively clean and how energy efficient it is in doing 
the cleaning. However, by running all tested air cleaners at maximum 
fan speed, the AHAM CADR Test fails to account for the energy-saving 
and other consumer benefits of air cleaners with this technology.

B. The Room Size Coverage Rule and IEF Rule Mislead Consumers

    In its response to Dyson's previous comments, DOE acknowledged that 
it was willing to accept inaccurate and inconsistent data because it 
was nevertheless important to have a test that DOE considered 
scientific, repeatable and easy to administer. DOE's decision, born of 
expedience at the cost of accuracy and consumer welfare, does not 
achieve DOE's goal of giving consumers relevant information about the 
energy efficacy and efficiency with which different air cleaners can 
clean various size rooms. To the contrary, it promotes consumer 
confusion by ignoring material differences in product features like 
active versus passive systems and systems that promote efficiency of 
use versus those that do not, as demonstrated by the new data 
highlighted by Dyson above and by Drs. Morse and Hashad in the Exponent 
Report.
    While Dyson sympathizes with DOE's desire to have a test that all 
industry participants can be held to that is repeatable, objective and 
capable of being implemented to ensure that manufacturers are not 
making claims lacking in scientific substantiation, the test must 
nevertheless provide relevant and accurate information to inform 
consumer purchasing decisions. A bad standardized test is worse than no 
standardized test. Consumers should be given accurate and reliable 
information that helps them answer two questions: (1) how effectively 
will the air cleaner clean the room where I will be using it, and (2) 
how efficiently will the air cleaner do that cleaning and at what cost 
in terms of its energy consumption? Room size coverage claims and IEF 
scores calculated using CADRs measured by the AHAM CADR Test--as 
mandated by the Room Size Coverage Rule and IEF Rule--fail to 
accurately answer either question.
    As is evident from Figure 8, below, as flaws in the AHAM CADR Test 
are corrected, the CADR scores for different products (and, therefore, 
room size coverage claims and IEF scores) vary dramatically. The 
significant variance (and drop in CADR scores for many products without 
features such as lateral whole-room air circulation technology) as 
real-world conditions are introduced into the test chamber, 
demonstrates that the gap between what consumers experience in `real 
life' vs. performance in the AHAM CADR Test chamber can be substantial. 
The Room Size Coverage Rule and IEF Rule inhibit a consumers' ability 
to identify an air cleaner that is the right size for their space in 
the real world, and to consider the energy consumption, cost and 
environmental impact of one air cleaner versus another.
[GRAPHIC] [TIFF OMITTED] TP30AP25.052


[[Page 17907]]



Figure 8.

------------------------------------------------------------------------
                                                             Room size
                                             Room size      capability
                                            capability       when real
                                            (AHAM CADR         world
                                           TEST method)   conditions are
                                               ft\2\        introduced
                                                               ft\2\
------------------------------------------------------------------------
Product A...............................             166             129
Product B...............................             285             281
Product C...............................             290             234
Product D...............................             142             109
------------------------------------------------------------------------

    For example, if a consumer wishes to purchase an air cleaner for 
his 280 ft\2\ living room, he would be influenced by Product C's 
claimed room size figure of 290 ft\2\ and perhaps purchase this 
product. However, when this consumer uses Product C in his home, he 
will not be using the product in the same conditions as found in the 
AHAM CADR Test chamber: he will not have a powerful recirculation fan 
and will likely place the product in the corner of an average-sized 
room--introducing simple real-world conditions that are not accounted 
for by the AHAM CADR Test and not reflected in room size coverage 
claims and IEF scores calculated using CADR.
    The performance experienced by the consumer using Product C in his 
home will be materially worse than what the consumer has been led to 
believe would be the performance by the air cleaner. Product C may only 
be able to effectively clean a space of 234 ft\2\--far smaller than 
what the consumer believed would be the effective room size coverage 
when purchasing the air cleaner in reliance on DOEmandated product 
performance claims. This mismatch between claims and reality will 
result in Product C taking a longer time to effectively clean the room 
it was advertised as being suited for, leading to increased energy 
consumption and energy costs when compared to what the consumer will 
have anticipated, as well as poorer performance. In some scenarios, the 
undersized air cleaner may not be able to clean the room at all.
    Product B (which scored slightly worse than Product C under AHAM 
CADR Test conditions and yet maintained the same score despite 
introduction of real-world conditions (dropping only from 285 ft\2\ to 
281 ft\2\)), will perform as well in the consumers' home as advertised 
pursuant to the Room Size Coverage Rule and IEF Rule. However, this 
does not help the consumer who has already purchased Product C, 
erroneously believing it will perform as well, or better than, Product 
B (and may have been sold at a lower price than Product B because it 
did not need to incorporate built-in air mixing and circulating 
technologies used by Product B in order to score comparatively well on 
the AHAM CADR Test).
    This is a problem. As DOE has acknowledged, the inability of 
consumers to select the right-sized air cleaners for their homes 
results in, among other things, energy inefficiency and increased 
energy consumption, in violation of DOE's remit to establish standards 
for energy efficiency:

    Room size would strongly impact the capacity of the air cleaner 
that would be required to clean the air in the desired room. For 
instance, if the air cleaner is too small compared to the size of 
the room it is being used in, it will be ineffective, thus providing 
low efficiency. Conversely, if an air cleaner is too big for the 
room that it is operated in, it will clean the air very quickly and 
continue operating, leading to increased energy use. Therefore, it 
is important that an air cleaner be selected such that its capacity 
(expressed in terms of its CADR) is appropriate for the size of the 
room that it is intended to be used in.51
---------------------------------------------------------------------------

    \51\ Energy Conservation Program: Test Procedures for Air 
Cleaners, 88 FR 14014 at 21 (Mar. 6, 2023).
---------------------------------------------------------------------------

C. The Room Size Coverage Rule And IEF Rule Stifle Innovation

    By failing to account for real-world conditions and, in particular, 
providing undeserved ``extra credit'' to air cleaners without lateral 
whole-room air circulation fans, room size coverage claims and IEF 
scores calculated using CADRs measured by the AHAM CADR Test provide 
insufficient and inaccurate differentiation between the performance of 
air cleaners that do have such technology and the performance of air 
cleaners that do not have such technology. Likewise, by not accounting 
for features like automatic sensor-response technologies that enable 
certain air cleaners to be more energy efficient, room size coverage 
claims and IEF scores calculated using the AHAM CADR Test prevent 
brands from competing for consumers based on those consumer- and 
environmentally-friendly technologies. This perverse situation not only 
leads to frustration of a consumers' ability to choose the right air 
cleaner for their homes, but also reduces manufacturers' incentive to 
continue to innovate to create better products that enhance consumer 
welfare. Why invest in innovation if, under the Room Size Coverage Rule 
and IEF Rule, air cleaners without performance and energy efficiency-
improving technologies appear to consumers to be equally effective and 
efficient as those products whose manufacturers have invested in 
researching and developing improved technologies?

D. The Room Size Coverage Rule and IEF Rule Result in Increased Energy 
Consumption

    The Energy Policy and Conservation Act of 1975 (``EPCA'') requires 
that any test procedures prescribed or amended by DOE shall be 
reasonably designed to produce test results which measure energy 
efficiency, energy use or estimated annual operating cost of a covered 
product, including air cleaners. (See 42 U.S.C. 6293(b)(3)). The Room 
Size Coverage Rule and IEF Rule fail to comply with the EPCA.
    Room size coverage claims and IEF scores compliant with the Room 
Size Coverage Rule and IEF Rule do not provide accurate information to 
consumers concerning the efficiency and efficacy of different air 
cleaners due to the multiple flaws in the AHAM CADR Test discussed 
above. As a result, consumers will unknowingly choose the wrong 
products for their rooms, resulting in increased energy consumption, as 
DOE itself acknowledged in the final rule.\52\
---------------------------------------------------------------------------

    \52\ Id. (``Room size would strongly impact the capacity of the 
air cleaner that would be required to clean the air in the desired 
room. For instance, if the air cleaner is too small compared to the 
size of the room it is being used in, it will be ineffective, thus 
providing low efficiency. Conversely, if an air cleaner is too big 
for the room that it is operated in, it will clean the air very 
quickly and continue operating, leading to increased energy use. 
Therefore, it is important that an air cleaner be selected such that 
its capacity (expressed in terms of its CADR) is appropriate for the 
size of the room that it is intended to be used in.'').
---------------------------------------------------------------------------

    Likewise, the Room Size Coverage Rule and IEF Rule perversely 
encourage rather than prevent greenwashing (i.e., false, deceptive or 
exaggerated claims about the environmental bona fides of a product that 
are apt to mislead consumers). The purported rationale for the Room 
Size Coverage Rule and IEF Rule is energy efficiency: ensuring that 
accurate room size claims and energy efficiency metrics are available 
to consumers so that they can make more informed purchasing decision 
and have clarity around expected energy consumption. This information 
inevitably also influences a consumer's perception of how `green' a 
particular product is, an important factor for many consumers today. As 
long as the Room Size Coverage Rule and IEF Rule rely on CADRs measured 
using the AHAM CADR Test, certain manufacturers and distributors of air 
cleaners will have an easy route to promote their products as `greener' 
than they are and claim that their products will achieve a level of 
performance that they will, in fact,

[[Page 17908]]

never achieve in a larger space (absent the purchase of a second air 
cleaner)--to the detriment of consumer welfare and DOE's remit to 
promote energy efficiency.

E. The Room Size Coverage Rule and IEF Rule Should Be, at Minimum, 
Stayed To Provide Time for Notice and Comment on Whether To Revoke or 
Modify the Rules

    Dyson recognizes that it is not possible to `exactly' replicate 
consumer conditions in every given scenario when designing a 
laboratory-based test method which is reliable, repeatable, and 
scalable for mass testing. To the extent DOE wants to maintain a 
standard rule for substantiation of room size coverage claims that is 
repeatable and scalable for mass testing yet more reliable in terms of 
giving consumers meaningful information about the efficacy and energy 
efficiency with which different air cleaners will clean various sized 
rooms, Dyson urges DOE to revoke the Room Size Coverage Rule and IEF 
Rule and open a period of notice and comment concerning alternative 
approaches to testing CADR. If, however, DOE is not inclined to revoke 
the Rules before opening a new period of notice and comment, DOE 
should, at minimum, stay enforcement of the Room Size Coverage Rule and 
IEF Rule.
    As discussed in detail in the Exponent Report, there may be 
relatively simple alterations to CADR testing that would narrow the gap 
between lab-based testing that is repeatable yet lacking in real-world 
relevancy, and testing which is more reflective of consumer 
environments, without compromising the ability to have a test that is 
repeatable and scalable. The Exponent Report discusses in Section 4.5 
the following types of modifications that would improve its real-world 
validity, among others:
    [ssquf] Adjustable chamber sizing.\53\
---------------------------------------------------------------------------

    \53\ See Exponent Report at p. 28.
---------------------------------------------------------------------------

    [ssquf] Elimination of the recirculation fan and installation of 
multiple sensors.\54\
---------------------------------------------------------------------------

    \54\ Id.
---------------------------------------------------------------------------

    [ssquf] Placement of the air cleaner in a corner of the 
chamber.\55\
---------------------------------------------------------------------------

    \55\ Id.
---------------------------------------------------------------------------

    Dyson has concerns that the desire to provide a one-size-fits-all 
test for room size coverage claims and IEF scores will always create 
more harm than good, and that any calculation relying on the AHAM CADR 
Test as its methodological foundation will fail to generate accurate 
and meaningful information that helps consumers discern which air 
cleaners on the market will most effectively and efficiently clean 
rooms of various sizes. Nevertheless, if DOE is inclined to require a 
standard test for room size coverage claims (if something truly is 
better than nothing in this context), Dyson respectfully submits that 
DOE revoke or, failing that, stay the Room Size Coverage Rule and IEF 
Rule and open a period of notice and comment so that interested parties 
can provide inputs to DOE concerning changes or substitutions that can 
be made to give room size coverage claims and IEF scores greater real-
world validity.

IV. Conclusion

    The Room Size Coverage Rule and IEF Rule require air cleaner 
manufacturers to make product claims that are neither accurate nor 
consistent, and that do not support energy efficiency. The Rules rely 
upon a test methodology that has significant shortcomings which result 
in inflated, inaccurate performance and energy efficiency claims, 
frustrating consumers' ability to make informed purchasing decisions 
and choose an air cleaner which is suitable for their homes. Further, 
the difference between the inflated performance and energy efficiency 
claims communicated to consumers under the Room Size Coverage Rule and 
IEF Rule, and the actual performance of air cleaners in real world 
conditions, results in consumers using more energy, and incurring more 
costs, to clean their spaces than they were led to believe.
    DOE needs to act now to reverse course on the Room Size Coverage 
Rule and IEF Rule and avoid continued misleading of consumers, stifling 
of innovation and wasteful energy consumption, as well as avoid the 
Rules' adoption by other regulators, including FTC, which would amplify 
the negative impact of the mandates and make them more difficult to 
unwind in the future.
    Accordingly, Dyson respectfully requests that DOE:
    1. Amend part 429 of chapter II, subchapter D, of title 10 of the 
Code of Federal Regulations to remove section 429.68(a)(4), and,
    2. Amend part 430 of chapter II, subchapter D, of title 10 of the 
Code of Federal Regulations to remove section 430.23(hh)(4), or in the 
alternative,
    3. Stay enforcement of 429.68(a)(4) and 430.23(hh)(4), and open a 
period of notice and comment to receive public comments on potential 
substitutions for room size coverage claims and IEF scores based on 
CADRs calculated using the AHAM CADR Test, or potential revisions that 
can be made to the AHAM CADR Test to better approximate real-world 
performance of air cleaners and to promote greater energy efficiency.

Sincerely,

Elena Stein,
General Counsel Dyson, Inc.

CC: United States Federal Trade Commission

[FR Doc. 2025-07351 Filed 4-29-25; 8:45 am]
BILLING CODE 6450-01-P